Voltage fluctuations
Testing performed per
EN 61000-4-11 61000-4-29
Test values per
EN 61131-2 (Zone B)
Test values per
EN 61000-6-2
AC mains inputs -15% +10%
Test duration per minutes
Criteria A
-
DC mains inputs -15% +20%
Test duration per minutes
Criteria A
-
98 Smart Camera Smart Sensor User's manual 1.5 periods (50/60 Hz) 1)
20 attempts
Criteria A
0% residual voltage
1 period (50/60 Hz) 1)
3 attempts
Criteria B
DC mains inputs residual voltage
≥10 (PS2) 2)
20 attempts
Criteria A
-
1) Mains frequency per manufacturer data
2) Use B&R power supply unit guarantees that these requirements are met.23
.International and national certifications
Voltage dips
Testing performed per
EN 61000-4-11
Test values per
EN 61131-2 (Zone B)
Test values per
EN 61000-6-2
0% residual voltage
250/300 periods (50/60 Hz) 1)
20 attempts
Criteria C
40% residual voltage
10/12 periods (50/60 Hz) 1)
20 attempts
Criteria C
AC mains inputs
70% residual voltage
25/30 periods (50/60 Hz) 1)
20 attempts
Criteria C
1) Mains frequency per manufacturer data
Short-term interruptions
Testing performed per
EN 61000-4-11 61000-4-29
Test values per
EN 61131-2 (Zone B)
Test values per
EN 61000-6-2
AC mains inputs residual voltage
0