International and national certifications
High-speed transient electrical disturbances (Burst)
Testing performed per
EN 61000-4-4
Test values per
EN 61131-2 (Zone B)
Test values per
EN 61000-6-2
AC mains inputs kHz
Criteria B
±2 kHz 100 kHz
Criteria B
AC mains outputs kHz
Criteria B
±2 kHz 100 kHz1)
Criteria B
Other inputs/outputs kHz
Criteria B
-
DC mains inputs/outputs kHz
Criteria B
±1 kHz 100 kHz
Criteria B
Other inputs/outputs and interfaces kHz
Criteria B
±1 kHz 100 kHz
Criteria B
1) Without length limitation.23 97
.5 kV
Criteria B
±0.
Conducted induced radio-frequency fields (RF-conducted)
Testing performed per
EN 61000-4-6
Test values per
EN 61131-2 (Zone B)
Test values per
EN 61000-6-2
AC mains inputs/outputs V
150 kHz MHz
80% kHz)
Criteria A
DC mains inputs/outputs V
150 kHz MHz
80% kHz)
Criteria A
Other inputs/outputs and interfaces 1)
150 kHz MHz
80% kHz)
Criteria A
1) Only for connections with permissible line length greater than m.5 1)
Criteria B
DC mains inputs/outputs >30 m
(line PE)
±0.5 kV
Criteria B
±1 1)
Criteria B
Unshielded signal connections >30 m
(line PE)
±1 kV
Criteria B
±1 kV
Criteria B
All shielded lines >30 m
(line PE)
±1 kV
Criteria B
-
1) Without length limitation.
Power frequency magnetic fields field)
Testing performed per
EN 61000-4-8
Test values per
EN 61131-2 (Zone B)
Test values per
EN 61000-6-2
Housing, completely wired A/m
3 axes (x, z)
50/60 1)
Criteria A
1) Mains frequency per manufacturer data
Smart Camera Smart Sensor User's manual 1.
Surge voltages (Surge)
Testing performed per
EN 61000-4-5
Test values per
EN 61131-2 (Zone B)
Test values per
EN 61000-6-2
AC mains inputs/outputs
(line line)
±1 kV
Criteria B
±1 kV
Criteria B
AC mains inputs/outputs
(line PE)
±2 kV
Criteria B
±2 kV
Criteria B
DC mains inputs/outputs >30 m
(line line)
±0