Od zkratu po oblouk hledání závady s AFDD

| Kategorie: Návody k obsluze Montážní návody  | Tento dokument chci!

Vydal: HAGER ELECTRO s.r.o.

Strana 4 z 5







Poznámky redaktora
H Contact the Technical support. standard electrical troubleshooting. 02 Hager LTD, Hortonwood 50,Telford-TF1 7FT, United Kingdom . Assumption: Internal AFDD error ► Replace the AFDD. Yellow flag presence Assumption: Overvoltage Check the electrical installation and/or the power supply. LED steady YELLOW LED steady RED Assumption: Residual current fault 0Only for RCBO-AFDD 1. Switch off load. AFDD manually tripped Yellow flag absence LED blinking RED/GREEN LED blinking RED/GREEN Overload Do standard electrical troubleshooting and check the appearance short- circuit overload.AFDD troubleshooting Handle ON. LED blinking YELLOW 03 Standard electrical troubleshooting Handle OFF. 2. LED OFF. Voltage between 216V (-6%) and 253V (+10%) Measure voltage of device. Voltage ok. T Voltage below 216V above 253V Replace the AFDD. Check the power supply voltage and/or connection to the AFDD. Handle OFF