If circuit and/or the enclosure measuring instrument auxiliary appliance designed for mains connection connected live parts the test assembly which can carry voltage to earth, then the internal insulation the supplying isolating transformer shall rated least to this voltage.ERECTION AND OPERATION ELECTRICAL TEST EQUIPMENT 95 11. 11. indicator lights. Protection against electric shock The test assembly shall arranged and designed that the protection against direct contact is secured insulation live parts, covers, enclosures, obstacles safe distances.3. Test equipment and test areas shall clearly and visibly indicated means warning signs.g.g.g. In case measuring instruments and auxiliary appliances protection Class (cathode ray oscilloscope, sine wave generator), where the protective conductor interrupted facilitate testing, e. An effective protective measure for protection case fault (protection against indirect contact) shall provided. safe distance ensured, when the person carrying out tests cannot reach the prohibition zone with parts his/her body tools. No clamping devices shall permitted for this purpose. . Where several persons are involved test, two- hand control device shall provided for each person the personnel and which are so connected that all the two hand controls are required operated before the test supplies can be energised. adequate number manual controls shall provided inside and outside the test area appropriate the size the area and complexity layout.3. Safety can also means two-hand control device the use of two safety probes apply the test voltage. because the enclosure has isolated from earth potential, the appliance shall be supplied from isolating transformer .1 Emergency switching off Test equipment shall provided with means for emergency switching off order cut off all electrical energy which could result danger. Connection points, e. outlets the general power supply within the test area, shall identified accordingly, they are not interrupted the emergency switching off equipment. Test equipment shall have devices which indicate the operational status, e. Safety test probes shall have the adequate insulation level for the applied test voltage. The test equipment controls and test circuits shall clearly identified. The test assembly shall designed and arranged order prevent the transfer of voltage extraneous conductive parts