m.2 Measures for protection automatic disconnection supply For all types systems earthing following fundamental principles shall applied: a) Earthing Exposed conductive parts shall connected the earth means protective conductor. .s. b) Conventional voltage limit The conventional voltage limit equal a.FUNDAMENTAL RULES FOR PROTECTION AGAINST ELECTRIC SHOCK 41 L1, L2, Phase conductors 1,2,3 or Line conductors 1,2,3 PE Protective conductor; N Neutral conductor; PEN PEN conductor.c. Symbols for conductors according IEC 617 (1983): protecctive conductor (PE) neutral conductor (N) PEN conductor (PEN) 5., r. 120 ripple-free d.c. Figure 5. the maximum prospective touch voltage which can occur exposed conductive parts under usual conditions for indefinite time.2.2.6 TN-C-S system: one part the system neutral and protective function are combined a single conductor, another part the system there are separate neutral and protective conductors.2