OPERATION ELECTRICAL INSTALLATIONS
88
10. These activities
include tending equipment and devices such switching, controlling, monitoring, well as
work electrical installation such maintenance and repairing and verification it.
Persons who are required work the vicinity electrical installations shall be
provided with training and information that they are able give appropriate first aid treatment
for electric shock and/or burns.)
All necessary information such network arrangement, state switchgear (on, off,
earthed), position safety device permit safe operation the electrical installation shall
normally transmitted Command B. OPERATION ELECTRICAL INSTALLATIONS
The operation electrical installations includes all activities necessary permit the
electrical installation function both under normal and abnormal conditions.
The principles for work activity near electrical installation not apply ordinary
persons for their own domestic electrical installation private dwellings and when using
equipment designed and installed for use ordinary persons which complies with relevant
standards.
The next information which Command according ČSN 3100 further contains are the
workplace, time and type work activities, name and signature person who gives the order
and names and signatures persons providing the safety stage workplace (switching off,
isolating and earthing it). (This person, according ČSN 3100, signs the
Command B.
Any tools, equipment, and devices provided for the purpose safe operation the
vicinity electrical installation shall suitable for that use, maintained good order and
properly used.
Before any work activity starts, the nominated person control the electrical installation
shall informed the intended work.
The preparation the work activity, except for simple and often repeated works, shall be
made written form (Command according ČSN 3100).
From the basic principles operation electrical installation choose following rules:
All activities the vicinity electrical installation shall subjected the
preparation and agreement the nominated person control the work activity and the
nominated person control the electrical installation.
Examples tools, equipment and devices are:
- insulating boots, gloves and overshoes;
- eye face protection;
- insulating mats, platforms and stands;
- insulated flexible and rigid screening materials;