Introduction to Electrical Engineering

| Kategorie: Kniha  | Tento dokument chci!

Pro: ČEKO IMPORT a.s.
Vydal: České vysoké učení technické Praha Autor: Vladimír Kůla, Michal Kříž

Strana 58 z 112

Jak získat tento dokument?






Poznámky redaktora
necessary because protective conductors have safety function.3.3. the application this table produces non-standard sizes, conductors having the nearest standard cross-sectional area are used. this not so, the cross-sectional area the protective conductor determined manner which produces conductance equivalent that which results from the application Table 6. Proper installation protective conductor It follows from the principles mentioned above that almost every electrical installation the conductor for mutual connection exposed conductive parts, extraneous parts, and earth, besides the live (phase) conductors, shall installed. This conductor called protective conductor and identified letters PE. These rules follow from the purpose protective connection provided them.3. The terminals for protective conductors shall much more reliable than terminals for other conductors.1. 6.3. Protective conductors well terminals for protective conductors shall fulfill certain rules. Protective conductors well the terminals connecting them shall sufficient cross- sectional area for conducting fault currents, usually short circuit currents, caused failure of installation and consequently short connection between live parts and exposed conductive parts the point failure. means that the safety depends electrical installation more less protective conductors.3.1. Table 6.1 Cross-sectional area phase conductors of the installations S (mm2 ) Minimum cross-sectional area the corresponding protective conductor (PE) Sp (mm2 ) S S 16 16 35 S/2 The values Table 6.CONSTRUCTION ELECTRICAL INSTALLATION AND EQUIPMENT 59 locating devices. The cross-sectional area the protective conductor shall not less than the appropriate value shown Table 6. The cross-sectional area every protective conductor, which does not form part the supply cable cable enclosure, shall be, any case, not less than: − 2,5 mm2 mechanical protection provided, .1 are valid only the protective conductor made the same material the phase conductors. case conductive floor around the high voltage device, the floor shall be connected with the exposed conductive parts the device