08
02 Requirements where
RCD’s are series
Where car charger supplied from existing
installation, from spare way the consumer unit,
we may consider installing shown below.
There however RCD upstream within the
consumer unit which also supplies other circuits.
A dedicated MCB installed the consumer unit to
feed Type RCCB for the car charging supply.3.
Sw/D/I
MCB
MCB
MCB
MCB
MCB
MCB
RCCB
RCCB
Spare
Spare
Spare
MCB
RCCB
Type.
This therefore would not satisfy the requirements of
722.101 and such should not used.531.
This design does have individual RCD supplying
the car charger