16
04 Product
Solutions
Due the requirements from 7671, suggest
the options shown this section for car charging
circuits.531.
Within the consumer unit the two options have
individual circuit protection which better satisfies
BS 7671 section 314, dividing circuits avoid
danger and minimize inconvenience. addition the
requirements 722.
. also important guidance from
the distribution board manufacturer sought a
car charger would constant load and the Rated
Diversity Factor (RDF) the distribution board may
need applied
In these solutions RDF applicable the circuit is
adjacent other continually loaded devices. Test
results from Hager have proved both these solutions
suitable using 40A devices and applying RDF
of 0.3.101 are satisfied with
the RCD being individual and not supplying other
circuits
Depending the charging manufacturer and the
wiring method, the circuit protection device the
distribution board will either need MCB a
double pole RCD.8