(Lightly loaded circuits i.
The protective device (MCB/RCBO) next it
would also need increased factor 2
(In/0.e.
Example
A 10-way consumer unit having MCB RCCB
adjacent the car charging circuit, where deemed
to continually loaded, the 7kW car charger will
require 63A rated protective device (MCB/RCBO).
.5). These rating factors could obviously have
implications associated cable sizing.15
A circuit will considered continually loaded
where the ‘on’ time the circuit exceeds minutes
or for cyclic loads where the ‘on’ time exceeds the
‘off’ time. lighting
circuit with LED luminaires will likely not count as
continually loaded)
The circuit supplying the car charger will clearly
be continually loaded. Should this protective
device adjacent another protective device
(this includes the main switch and RCCB) that
is also continually loaded then they are both now
simultaneously loaded and will require the factor to
be applied