Electric Vehicle Charging

| Kategorie: Leták / Datasheet  | Tento dokument chci!

Vydal: HAGER ELECTRO s.r.o.

Strana 15 z 18







Poznámky redaktora
(Lightly loaded circuits i. The protective device (MCB/RCBO) next it would also need increased factor 2 (In/0.e. Example A 10-way consumer unit having MCB RCCB adjacent the car charging circuit, where deemed to continually loaded, the 7kW car charger will require 63A rated protective device (MCB/RCBO). .5). These rating factors could obviously have implications associated cable sizing.15 A circuit will considered continually loaded where the ‘on’ time the circuit exceeds minutes or for cyclic loads where the ‘on’ time exceeds the ‘off’ time. lighting circuit with LED luminaires will likely not count as continually loaded) The circuit supplying the car charger will clearly be continually loaded. Should this protective device adjacent another protective device (this includes the main switch and RCCB) that is also continually loaded then they are both now simultaneously loaded and will require the factor to be applied