ABB Softstartéry - komunikace (EN)

| Kategorie: Leták / Datasheet  | Tento dokument chci!

Vydal: ABB s.r.o, ELSYNN Autor: ABB ELSYnn

Strana 5 z 225







Poznámky redaktora
00 EDS_PST_Rev4_5. Through the fieldbus ispossibleto start and stopthe motor, perform jog, sequence start, read out currents and frequency, achieve information about protections, warnings, faults and much more. For technical data and descriptions the DeviceNet fieldbus plug, see document 2CDC193001D0203, available www. See chapter “Setting and configuration” the installation manual for programming the inputs outputs.eds CU 03.com/lowvoltage .04.01 and 03.03. Before the DeviceNet fieldbus can taken operation following parameters must set the softstarter: ■ Parameter Fieldbus Ctrl set Yes ■ Parameter Fieldbus Type set other ■ Parameter Fieldbus Addr set free communication address. To the programming the PLC, following EDS files are available: Softstarter CU-version EDS file CU 02.05.01 EDS_PST_Rev4_0.eds CU 03.02 EDS_PST_Rev4_4.DeviceNet The DeviceNet protocol fieldbus protocol that provides full controland statusinformation the softstarter as well reading and writing parameters.abb.eds ACaution! The motor may start unexpectedly there start signalpresent when doing any the actions listed below. • Switchingfrom one type control another (fieldbus control hardwire control) • Re-programming the programmable inputs • Reset all Settings (programmable input set Enable) 1SFC132012M0201.00