Type Parameter Description Range Unit
23 Read/Write Underl Lev Trip level for Underload protection 0,4 0,8 xle
24 Read/Write Underl Time Trip time for Underload protection Sec
25 Read/Write Underl Type operation for Underload protection Stop-M, Stop-A, Ind
26 Read/Write Phase Imb Phase imbalance protection No, Yes
27 Read/Write Imb Lev Trip level for phase imbalance protection %
28 Read/Write Imb Op
Type operation for phase imbalance
protection Stop-M, Stop-A, Ind
29 Read/Write High High current protection No, Yes
30 Read/Write High Type operation for high current protection Stop-M, Stop-A, Ind
31 Read/Write Phase Rev Phase reversal protection No, Yes
32 Read/Write Rev Op
Type operation for phase reversal
protection Stop-M, Stop-A, Ind
33 Read/Write PTC PTC protection No, Yes
34 Read/Write PTC Type operation for PTC protection Stop-M, Stop-A, Ind
35 Read/Write Ext ByPass External By-pass contactor used No, Yes
36 Read Dummy Hidden (Not used) 0
37 Read/Write Warn I=High High current warning No, Yes
38 Read/Write I=H Lev Trip level for high current warning
O,
00
1
m
o'
xle
39 Read/Write Warn I=Low Low current warning No, Yes
40 Read/Write I=L Lev Trip level for low current warning 0,4 1,0 xle
41 Read/Write Warn Overload warning No, Yes
42 Read/Write Lev Trip level for overload warning %
43 Read/Write
Warn SCR
OL Thyristor overload warning No, Yes
44 Read/Write Loss Type operation for phase loss fault Stop-M, Stop-A
45 Read/Write Fault Type operation for fieldbus fault Stop-M, Stop-A
46 Read/Write Freq Op.
56 Raed/Write Event K5
Different events include for signalling with
K5 “Event” selected
0 65535, Bit mask see
separate description.
59 Read Fieldb Ctrl Control the softstarter with fieldbus No, Yes
60 Read Fieldb Type Type fieldbus AS-Int, Other
61 Read Fieldb Addr Fieldbus address 1000
62 Read/Write Seq Number sequences for sequence start. No, 3
63 Read/Write Start Rampl 1st sequence, time for start ramp -120 Sec
64 Read/Write Init Voltl 1st sequence, initial voltage for start ramp %
65 Read/Write Curr Liml 1st sequence, current limit 1,5 7,0 xle
66 Read/Write lst Set 1st sequence, motor rated current 3000 (*) Amp
67 Read/Write Start Ramp2 2nd sequence, time for start ramp -120 Sec
68 Read/Write Init Volt2 2nd sequence, initial voltage for start ramp %
69 Read/Write Curr Lim2 2nd sequence, current limit 1,5 7,0 xle
1SFC132051M0201 11
. Type operation for frequency fault Stop-M, Stop-A
47 Read/Write Temp Op
Type operation for heat sink over
temperature fault Stop-M, Stop-A
48 Read/Write SCR Op
Type operation for thyristor short circuit
fault Stop-M, Stop-A
49 Read In0 Function programmable input In0
None, Reset, Enable, Jog,
DOL-on, Start2, FB-Dis
50 Read Inl Function programmable input In1
None, Reset, Enable, Jog,
DOL-on, Start3, FB-Dis
51 Read/Write Relay Function programmable relay output Run, TOR, Event
52 Read/Write Relay Function programmable relay output Run, TOR, Event
53 Read/Write Relay Function programmable relay output Run, TOR, Event
54 Read/Write Outp Function programmable software output Run, TOR, Event
55 Read/Write Event K4
Different events include for signalling with
K4 “Event” selected
0 65535, Bit mask see
separate description.
58 Read/Write Event V7
Different events include for signalling with
V7 “Event” selected
0 65535, Bit mask see
separate description.
57 Read/Write Event K6
Different events include for signalling with
K6 “Event” selected
0 65535, Bit mask see
separate description