ABB Softstartéry - komunikace (EN)

| Kategorie: Leták / Datasheet  | Tento dokument chci!

Vydal: ABB s.r.o, ELSYNN Autor: ABB ELSYnn

Strana 195 z 225







Poznámky redaktora
Through the fieldbus possible start and stop the motor, perform jog, sequence start, read out currents and frequency, achieve information about protections, warnings, faults and much more.gsd Profibus V1 Note that the GSD file contains information about different software versions the softstarter.abb. To the programming the PLC, following GSD files are available: GSD file Type protocol ABB_078F. Check that correct part the file used relation the actual softstarter version.Profibus V1 The Profibus protocols are fieldbus protocols that provides full control and status information the softstarter well writing parameters (read and write for V1). ACaution! The motor may start unexpectedly there start signalpresent when doing any the actions listed below. See chapter “Setting and configuration” the installation manual for programming the inputs outputs. Before the Profibus fieldbus can taken operation following parameters must set the softstarter: ■ Parameter Fieldbus Ctrl set Yes ■ Parameter Fieldbus Type set other ■ Parameter Fieldbus Addr set free communication address. • Switchingfrom one type control another (fieldbus control hardwire control) • Re-programming the programmable inputs • Reset all Settings (programmable input set Enable) 1SFC132051M0201.com/lowvoltage . For technical data and descriptions the Profibus fieldbus plug, see document 2CDC192001D0205, available www.gsd Profibus V0 ABB_082d