Poznámky redaktora
04. Send configuration data the softstarter (Number I/O number parameters, etc.04 For other versions software RED marked figures this example will change Softstarter settings 1. Set the softstarter address and field bus communication. The communication parameters are: Start bit, Data bits, the Parity will adapted the master. Change the default address 248 the softstarter with the keypad (Fieldb Addr) and enable the fieldbus communication Fieldb Ctrl=Yes ).this particular example following documents has been used: Modbus RTU FBP FielBusPlug MRP21.). After the configuration the softstarter will regular Modbus slave (LED off) and will respond the polling telegrams the master. the baud rate the slave is 19200. 2. Softstarters PST installation and commissioning manual SFC132003M0201, June 2007 Softstarter software version: Ver 05. Therefore the master and the slave will have the communication parameters: 1 start bit, stop bit, data bit, even parity, 19200 baud Data exchange with the Modbus RTU master Step1 Without receiving the configuration data the softstarter not responding the request telegrams the Master (LED the FBP blinking). Step 2 Now the master can send different Modbus telegrams order exchange data with the Softstarter.g. Set the communication parameters. FBP technical description 2CDC194001D0201. 1SFC132050M0201 11 . The baud rate mapped the slave address, e