ABB Softstartéry - komunikace (EN)

| Kategorie: Leták / Datasheet  | Tento dokument chci!

Vydal: ABB s.r.o, ELSYNN Autor: ABB ELSYnn

Strana 188 z 225







Poznámky redaktora
Set the softstarter address and field bus communication.g. Send configuration data the softstarter (Number I/O number parameters, etc. Set the communication parameters. 2. Step 2 Now the master can send different Modbus telegrams order exchange data with the Softstarter.this particular example following documents has been used: Modbus RTU FBP FielBusPlug MRP21. 1SFC132050M0201 11 . the baud rate the slave is 19200.04. Change the default address 248 the softstarter with the keypad (Fieldb Addr) and enable the fieldbus communication Fieldb Ctrl=Yes ).). Softstarters PST installation and commissioning manual SFC132003M0201, June 2007 Softstarter software version: Ver 05. After the configuration the softstarter will regular Modbus slave (LED off) and will respond the polling telegrams the master.04 For other versions software RED marked figures this example will change Softstarter settings 1. The baud rate mapped the slave address, e. The communication parameters are: Start bit, Data bits, the Parity will adapted the master. FBP technical description 2CDC194001D0201. Therefore the master and the slave will have the communication parameters: 1 start bit, stop bit, data bit, even parity, 19200 baud Data exchange with the Modbus RTU master Step1 Without receiving the configuration data the softstarter not responding the request telegrams the Master (LED the FBP blinking)