Poznámky redaktora
Analogue input telegram To PLC from Softstarter. Channel Parameter No 14 Diagn. 12 Diagn. Word input data area Analogue input word Data Representation 3 Phase current Value =1000 1000A 4 Phase current Value =1000 1000A 5 Phase current Value =1000 1000A 6 Max phase current Value =1000 1000A 7 Measured frequency Value =100 100Hz 8 Output voltage Value =100 100% 9 Calc. Each channel consists two bytes with an error code and the parameter number that caused the error. Diagnostic inputs There are channels available for fieldbus related diagnostic messages. Channel Parameter No 13 Diagn. Motor temp. Channel Parameter No 1SFC132050M0201. Channel Error Code Diagn. Error Codes: Parameter Value out range 2 Invalid parameter No 3 Write parameter when fieldbus control isn’t enabled Word input data area Diagnostic input word Error Code Parameter No. All analogue data will represented bit values. Value =100 100% 10 Counted Starts Value =100 10000 times 11 Run Time Value =100 1000 hours *) Phase current L1, and indicates the current through the softstarter while the Max phase current always the line current. The latest error stored channel the second latest channel and the third latest channel The binary output bit “reset active diagnostics” used clear the diagnostic area. Channel Error Code Diagn. Channel Error Code Diagn