Poznámky redaktora
gsd Profibus V0
ABB_082d.
• Switchingfrom one type control another (fieldbus control hardwire control)
• Re-programming theprogrammable inputs
• Reset all Settings (programmable input set Enable)
1SFC132048M0201.
For technical data and descriptions the Profibus fieldbus plug, see document 2CDC192001D0205,
available www.Profibus V1
The Profibus protocols are fieldbus protocols that provides full control and status information the
softstarter well writing parameters (read and write for V1).
See chapter “Setting and configuration” the installation manual for programming the inputs outputs.com/lowvoltage .gsd Profibus V1
Note that the GSD file contains information about different software versions the softstarter.
Before the Profibus fieldbus can taken operation following parameters must set the softstarter:
■ Parameter Fieldbus Ctrl set Yes
■ Parameter Fieldbus Type set other
■ Parameter Fieldbus Addr set free communication address.abb.
ACaution!
The motor may start unexpectedly there start signalpresent when doing any the actions listed below. Through the fieldbus possible start and
stop the motor, perform jog, sequence start, read out currents and frequency, achieve information about
protections, warnings, faults and much more.
Check that correct part the file used relation the actual softstarter version.
To the programming the PLC, following GSD files are available:
GSD file Type protocol
ABB_078F