RTU-HTemp Display

| Kategorie: Leták / Datasheet  | Tento dokument chci!

Vydal: HW group s.r.o.

Strana 5 z 18







Poznámky redaktora
– the sensor installed the middle the RS-485 bus, set both switches the position opposite the ON marking (OFF position). 3) Routing Keep communication signal lines separate from 230 power lines. .HW-group. RS-485 line termination configured using DIP switch SW2. Star ring topologies are not permitted, they cause signal reflections and degrade communication quality. Do not route them the same conduit near high-current cables prevent electromagnetic interference (EMI). The shield should properly grounded one point only. 2) Cabling Use shielded twisted-pair (STP) cable for the RS-485 communication lines and B). 4) Termination The RS-485 line must terminated both ends. – the sensor used standalone device is located the end the RS-485 bus (daisy-chain topology), set both switches the position.com 18 RS-485 Network Installation Guidelines To ensure stable and reliable communication, follow these recommendations when installing the RS-485 network: 1) Topology Always use bus (daisy-chain) topology