Poznámky redaktora
the respec­ tive time maintenance, the various causes the decrease illuminance must be identified. According the formula below (1), light- ing level required 500 standard maintenance factor 0. Em: maintained illuminance = maintenance value illuminance (1) Enew Maintenance factor components – Lamp luminous flux mainten. The maximum each case 1, corresponding the new value. All these factors describe the decrease in illumi­ nance.194 The Lighting Handbook Maintenance lighting systems Today, the maintenance lighting installa- tions decisive factor installation’s balance costs. factor LLMF – Lamp survival factor LSF – Luminaire maintenance factor LMF – Room maintenance factor RMF Causes illuminance decrease – Ageing lamps – Failure lamps – Soiling luminaire – Soiling room The maintenance factor includes 4 components (2) LLMF LSF LMF RMF Benefit high MF – lower luminaire investment costs – reduced energy costs Benefit low MF – low maintenance costs – longer maintenance intervals Please note: lower maintenance factor, illuminance may constantly dimmed the maintenance value save energy (maintenance control).67 implies a new illuminance level Enew 750 lx. Options for improving the maintenance factor – lamp replacement already before the lamp service life ends (LLMF/LSF ) – immediate replacement lamps case of failure (LSF 1) – use closed luminaires (LWF7 ) – more frequent room cleaning (RWF7 ) ➝ ➝ ➝