The Lighting Handbook ZG

| Kategorie: Firemní tiskovina  | Tento dokument chci!

Vydal: ZG Lighting Czech Republic s.r.o

Strana 182 z 244







Poznámky redaktora
The specific range and type, well as, the actual number of ballasts per luminaire must taken into account. case metal halide lamps, the switch-on current increased ignition time shunting. Please note: the values given the table are intended reference values only and may deviate individual cases. case connection circuit breakers with characteristics, transformers should not loaded above rating order to avoid false tripping. The levels indicated the table refer simulta- neous switch-on the mains voltage peak with 230 V. Tripping characteristics Tripping current B (quick-acting) C 3 5-fold rated current 5 10-fold rated current . case multipolar circuit breakers, the values specified the manu- facturer must reduced 20%.182 The Lighting Handbook Fusing and rating circuits Tripping values line circuit-breakers For the operation luminaires, automatic circuit breakers with characteristics are recommended