The Lighting Handbook ZG

| Kategorie: Firemní tiskovina  | Tento dokument chci!

Vydal: ZG Lighting Czech Republic s.r.o

Strana 182 z 244







Poznámky redaktora
case multipolar circuit breakers, the values specified the manu- facturer must reduced 20%. Please note: the values given the table are intended reference values only and may deviate individual cases.182 The Lighting Handbook Fusing and rating circuits Tripping values line circuit-breakers For the operation luminaires, automatic circuit breakers with characteristics are recommended. case metal halide lamps, the switch-on current increased ignition time shunting. The levels indicated the table refer simulta- neous switch-on the mains voltage peak with 230 V. Tripping characteristics Tripping current B (quick-acting) C 3 5-fold rated current 5 10-fold rated current . case connection circuit breakers with characteristics, transformers should not loaded above rating order to avoid false tripping. The specific range and type, well as, the actual number of ballasts per luminaire must taken into account