The Lighting Handbook ZG

| Kategorie: Firemní tiskovina  | Tento dokument chci!

Vydal: ZG Lighting Czech Republic s.r.o

Strana 127 z 244







Poznámky redaktora
cable length DALI Max. The system can thus flexibly adjusted if the requirements the building change. 3 DALI incl.75 mm² 150 150 350 m 1. 50022) Space for only units required .00 mm² 200 200m 420 m 1. DALI voltage supply with 120 bus loads (240mA) per DALI line 64 DALI units per DALI line 64 DALI units per DALI line 1 system bus (without bus power supply) Test switch and status LED for each DALI chain 1 Ethernet 100Mbits/s; RJ45/CAT Connection Plug-in screw terminals for one-wire fine-wire cables with cross-section ranging from 0. first generation LITECOM infinity system can comprise 2,500 addresses with to 15 controllers and ultimately to 100,000 addresses will possible.50 mm² 100 100 250 m 0. cable length LM Jointly with mains Jointly with mains in the same cable the same cable 0.5 1. Permissible cable lengths Cable cross-section Max.5 mm Type installation DIN rail mounting (35mm DIN rail acc.50 mm² 300 300m 500 m System limit 250 addresses per LITECOM CCD 2,500 addresses with controllers the first LITECOM infinity generation, 100,000 addresses the final expansion stage.127 The Lighting Handbook LITECOM infinity: General information Technical data Application The number possible addresses adds by linking several LITECOM controllers