The Lighting Handbook ZG

| Kategorie: Firemní tiskovina  | Tento dokument chci!

Vydal: ZG Lighting Czech Republic s.r.o

Strana 105 z 244







Poznámky redaktora
– With DSI, units are allocated groups by wiring; with DALI, group allocation is performed via software.105 The Lighting Handbook DSI: General information – The term DSI stands for “Digital Serial Interface”. – Devices with DSI and DALI connection are not compatible and cannot used jointly in one control circuit. – With DSI (and 1–10 V), only unidirec­ tional flow information (from the controller to the controlled unit) possible. Differences between DALI and DSI – Each DALI control unit may have different intensity levels, while all DSI (and 1–10 V) control units always have the same inten- sity level. – DSI manufacturer-specific interface defined Zumtobel. DSI: Features – Usable data transmission rate: 1200 bit/s – Depending the output module: 10 100 control units per control circuit – Max. – DSI and DALI units cannot operated jointly one control circuit. – DSI the predecessor DALI with the main goal replacing analogue addressing (1–10 control gear with digital addressing. – DSI not building management bus sys- tem, but protocol for digital addressing of technical lighting control gear. scenes per control unit can be programmed – Unidirectional: reports only faulty lamps (depending the technical design the electronic ballast) – Two-wire control line (potential-free, polarity-free, unshielded, terminal resis­tors) – Application: general lighting (small number of lighting points, static light)