com Page 13
9.25A (T) rated fuse should installed line with terminal A1
Frequency range (AC supply): 50/60Hz
Supply variation: 115% Us
Auxiliary supply galvanically isolated from the Toroid and Remote Test/Reset connections
Overvoltage category: III (IEC 60664)
Rated impulse withstand voltage: 4kV (1.5mm wide cable tie (not supplied). before tripping) the
external toroid disconnected.tele-online. The unit factory set 30mA (or 6mA) (and instantaneous delay).5s, 5s, 10s
1 actual delay when set (instantaneous) <25ms I∆n
Note:
1.S., any other delay cannot set)
2. Adjustment these settings can be
made necessary, suit the requirements the installation.ELR01PN ELR30PN Earth Leakage Relay (Type with NFC Technology
TELE_ELR_PN-1-A_DS www. LED will also flash prior unit
reclosing “auto-reclosure” mode enabled.
. Technical Specification
Auxiliary Power Supply (5, 7)
Voltage rating (Us): 230V AC/DC
1.e. For I∆n 30mA less (model dependant) the Time delay fixed (instantaneous) and not
adjustable (i. prevent tampering the settings, the
clear window can secured place using 2mm 2.5mA 7.): AC: 6VA, DC: 5W
Monitored input (via external Toroid connected terminals and 9)
Unit classification: Type A
Measurement principle: True R.5mA 30A
User adjustments
External Toroid ratio: Selectable between 600:1 and 1000:1 100:1
steps
(factory default 1000:1)
Monitored leakage current range: ELR01PN ELR30PN
Trip level settings (I∆n): 6mA, 10mA, 30mA, 50mA,
100mA, 200mA, 300mA,
500mA, 750mA, 1A
30mA, 100mA, 300mA,
500mA, 1A, 3A, 5A,
10A, 20A, 30A
Actual trip level: 85% I∆n (+/- 5%)
Rated residual non-operating current (I∆no): <80% I∆n
Reset level: 85% tripped level
Time delay (Non-operate) settings (∆t): 01, 60ms, 150ms, 250ms, 500ms, 800ms, 1s,
2.
Input DSP filter cut-off 150, 300 450Hz
(factory default 150Hz)
External Toroid ratio: Selectable between 600:1 and 1000:1 100:1
steps
(factory default 1000:1)
Monitored leakage current range: ELR01PN ELR30PN
1.2/50µS) IEC 60664
Power consumption (max.e.
Reset time: <1s (from supply interruption)
LED indication (refer also LED status table page 6)
Power Supply Green x1
LED usually permanently lit but will flash valid profile has
been selected there was communication error with the
smartphone
Bargraph (25, 50, 75%) Yellow x3
Tripped Red 1
LED flashes during time out (i.M