5. LEISTUNGSSCHALTER “B” SCHLIESSEN UND KONTROLLIEREN, DASS DER LEISTUNGSSCHALTER “A” NICHT
GESCHLOSSEN WERDEN KANN. RÉARMER LES RESSORTS COMMANDE VÉRIFIER QUE DISJONCTEUR RESTE FERMÉ. REARME LOS MUELLES DEL MANDO “A” COMPRUEBE QUE ESTE INTERRUPTOR PERMANEZCA CERRADO.com
.abb.
2. CIERRE INTERRUPTOR “A” CONTROLE QUE INTERRUPTOR PUEDA CERRARSE.306-433
http://www.111 Telefax: +39 035 395.p. FERMER DISJONCTEUR CONTRÔLER QUE DISJONCTEUR PEUT PAS ÊTRE FERMÉ. FERMER DISJONCTEUR CONTRÔLER QUE DISJONCTEUR PEUT PAS ÊTRE FERMÉ.: +39 035 395.
4. CIERRE INTERRUPTOR “B” CONTROLE QUE INTERRUPTOR “A” PUEDA CERRARSE. CLOSE THE “B” CIRCUIT-BREAKER AND MAKE SURE THAT THE “A” CIRCUIT-BREAKER CANNOT CLOSED.
2. LEISTUNGSSCHALTER “A” SCHLIESSEN UND KONTROLLIEREN, DASS DER LEISTUNGSSCHALTER “B” NICHT
GESCHLOSSEN WERDEN KANN.
2. TERMINE DEI TEST VERIFICARE REGOLAZIONI BLOCCAGGIO DEI
TIRANTI.
4.
4.
2. FEDERN DES ANTRIEBS VON “A” ZURÜCKSTELLEN UND ÜBERPRÜFEN, DASS DER LEISTUNGSSCHALTER “A”
GESCHLOSSEN BLEIBT
3. RIARMARE MOLLE DEL COMANDO “A” VERIFICARE CHE L'INTERRUTTORE “A” RIMANGA CHIUSO
3. RÉPÉTER TEST FOIS.
3. FEDERN DES ANTRIEBS VON “B” ZURÜCKSTELLEN UND ÜBERPRÜFEN, DASS DER LEISTUNGSSCHALTER “B”
GESCHLOSSEN BLEIBT.
5. FIN DES TESTS, VÉRIFIER LES RÉGLAGES BLOCAGE DES TIRANTS
CONTROL MECÁNICO
RESTABLECER LOS RESORTES LOS MANDOS LOS INTERRUPTORES EFECTUAR LAS SIGUIENTES
OPERACIONES:
1. RIPETERE TEST PER VOLTE. CLOSE THE “A” CIRCUIT-BREAKER AND MAKE SURE THAT THE CIRCUIT-BREAKER CANNOT CLOSED.
A i
M m
ABB SACE S.ZB
CONTROLLO MECCANICO
RIARMARE MOLLE DEI COMANDI DEGLI INTERRUTTORI ESEGUIRE SEGUENTI OPERAZIONI:
1.
MECHANICAL CHECK
RESET THE CIRCUIT-BREAKERS OPERATING MECHANISM SPRINGS AND PERFORM THE FOLLOWING OPERATIONS:
1.A. REARME LOS MUELLES DEL MANDO “B” COMPRUEBE QUE ESTE INTERRUPTOR PERMANEZCA CERRADO
5.
4.
3. TEST DREI MAL WIEDERHOLEN.
CONTROLE MECANIQUE
REARMER LES RESSORTS DES COMMANDES DES DISJONCTEURS EFFECTUER LES OPERATIONS SUIVANTES:
1. CHIUDERE L'INTERRUTTORE “A” CONTROLLARE CHE L'INTERRUTTORE “B” NON POSSA ESSERE CHIUSO. RIARMARE MOLLE DEL COMANDO “B” VERIFICARE CHE L'INTERRUTTORE “B” RIMANGA CHIUSO
5.
MECHANISCHE KONTROLLE
DIE FEDERN DER ANTRIEBE DER LEISTUNGSSCHALTER WIEDER SPANNEN UND FOLGENDE SCHALTUNGEN
AUSFÜHREN:
1. RESET THE SPRINGS THE CIRCUIT-BREAKER CONTROL AND MAKE SURE THAT THE “B” CIRCUIT-BREAKER
REMAINS CLOSED
5. REPEAT THE TEST THREE TIMES, THEN CHECK THE ADJUSTMENTS AND THE FASTNESS THE TIE-RODS.
2. RESET THE SPRINGS THE “A” CIRCUIT-BREAKER CONTROL AND MAKE SURE THAT THE “A” CIRCUIT-BREAKER
REMAINS CLOSED
3. RÉARMER LES RESSORTS COMMANDE VÉRIFIER QUE DISJONCTEUR RESTE FERMÉ. CHIUDERE L'INTERRUTTORE “B” CONTROLLARE CHE L'INTERRUTTORE “A” NON POSSA ESSERE CHIUSO
4. REPITA PRUEBA OTRAS TRES VECES LUEGO, COMPRUEBE LOS AJUSTES BLOQUEO LOS TIRANTES.