4.ZB
CONTROLLO MECCANICO
RIARMARE MOLLE DEI COMANDI DEGLI INTERRUTTORI ESEGUIRE SEGUENTI OPERAZIONI:
1. FEDERN DES ANTRIEBS VON “A” ZURÜCKSTELLEN UND ÜBERPRÜFEN, DASS DER LEISTUNGSSCHALTER “A”
GESCHLOSSEN BLEIBT
3.
A i
M m
ABB SACE S.
MECHANICAL CHECK
RESET THE CIRCUIT-BREAKERS OPERATING MECHANISM SPRINGS AND PERFORM THE FOLLOWING OPERATIONS:
1.
4. FERMER DISJONCTEUR CONTRÔLER QUE DISJONCTEUR PEUT PAS ÊTRE FERMÉ. CLOSE THE “A” CIRCUIT-BREAKER AND MAKE SURE THAT THE CIRCUIT-BREAKER CANNOT CLOSED. FERMER DISJONCTEUR CONTRÔLER QUE DISJONCTEUR PEUT PAS ÊTRE FERMÉ.
3. FEDERN DES ANTRIEBS VON “B” ZURÜCKSTELLEN UND ÜBERPRÜFEN, DASS DER LEISTUNGSSCHALTER “B”
GESCHLOSSEN BLEIBT. CIERRE INTERRUPTOR “A” CONTROLE QUE INTERRUPTOR PUEDA CERRARSE. RESET THE SPRINGS THE “A” CIRCUIT-BREAKER CONTROL AND MAKE SURE THAT THE “A” CIRCUIT-BREAKER
REMAINS CLOSED
3.abb.
2.
2. REPITA PRUEBA OTRAS TRES VECES LUEGO, COMPRUEBE LOS AJUSTES BLOQUEO LOS TIRANTES.111 Telefax: +39 035 395. RÉARMER LES RESSORTS COMMANDE VÉRIFIER QUE DISJONCTEUR RESTE FERMÉ.
5.p.306-433
http://www. LEISTUNGSSCHALTER “A” SCHLIESSEN UND KONTROLLIEREN, DASS DER LEISTUNGSSCHALTER “B” NICHT
GESCHLOSSEN WERDEN KANN.
5. CLOSE THE “B” CIRCUIT-BREAKER AND MAKE SURE THAT THE “A” CIRCUIT-BREAKER CANNOT CLOSED. RESET THE SPRINGS THE CIRCUIT-BREAKER CONTROL AND MAKE SURE THAT THE “B” CIRCUIT-BREAKER
REMAINS CLOSED
5.com
.
4.
Via Baioni, 35
24123 Bergamo Italy
Tel.
4.
2. REARME LOS MUELLES DEL MANDO “A” COMPRUEBE QUE ESTE INTERRUPTOR PERMANEZCA CERRADO.
MECHANISCHE KONTROLLE
DIE FEDERN DER ANTRIEBE DER LEISTUNGSSCHALTER WIEDER SPANNEN UND FOLGENDE SCHALTUNGEN
AUSFÜHREN:
1. TERMINE DEI TEST VERIFICARE REGOLAZIONI BLOCCAGGIO DEI
TIRANTI. REARME LOS MUELLES DEL MANDO “B” COMPRUEBE QUE ESTE INTERRUPTOR PERMANEZCA CERRADO
5. FIN DES TESTS, VÉRIFIER LES RÉGLAGES BLOCAGE DES TIRANTS
CONTROL MECÁNICO
RESTABLECER LOS RESORTES LOS MANDOS LOS INTERRUPTORES EFECTUAR LAS SIGUIENTES
OPERACIONES:
1.
2. RÉARMER LES RESSORTS COMMANDE VÉRIFIER QUE DISJONCTEUR RESTE FERMÉ. CIERRE INTERRUPTOR “B” CONTROLE QUE INTERRUPTOR “A” PUEDA CERRARSE. LEISTUNGSSCHALTER “B” SCHLIESSEN UND KONTROLLIEREN, DASS DER LEISTUNGSSCHALTER “A” NICHT
GESCHLOSSEN WERDEN KANN.
2.
CONTROLE MECANIQUE
REARMER LES RESSORTS DES COMMANDES DES DISJONCTEURS EFFECTUER LES OPERATIONS SUIVANTES:
1. RIARMARE MOLLE DEL COMANDO “A” VERIFICARE CHE L'INTERRUTTORE “A” RIMANGA CHIUSO
3. CHIUDERE L'INTERRUTTORE “B” CONTROLLARE CHE L'INTERRUTTORE “A” NON POSSA ESSERE CHIUSO
4. TEST DREI MAL WIEDERHOLEN.
3.: +39 035 395. CHIUDERE L'INTERRUTTORE “A” CONTROLLARE CHE L'INTERRUTTORE “B” NON POSSA ESSERE CHIUSO.A. RIARMARE MOLLE DEL COMANDO “B” VERIFICARE CHE L'INTERRUTTORE “B” RIMANGA CHIUSO
5. REPEAT THE TEST THREE TIMES, THEN CHECK THE ADJUSTMENTS AND THE FASTNESS THE TIE-RODS. RIPETERE TEST PER VOLTE. RÉPÉTER TEST FOIS