Poznámky redaktora
1SDH000635R0002
Page No.6 Test Menu
Access the Test menu password protected.
- Value the current has tripped.
In any case, functionality the relay way modified the presence the wear messages. connecting
a PR030/B battery unit and PR010/T BT030 wireless communication unit, you can retrieve the information relating the last trips recorded. 800 A
Installation June 12, 2007
Maintenance June 12, 2007
About 1/2
13.
Again the Measurements menu, you can view the percentage contact wear, which indication the electrical life the electrical contacts
in the circuit-breaker. There need for auxiliary power supply for this function.
On the page only with Vaux, you can also see the state the circuit-breaker "STATUS", and thus make sure that the input correctly wired.
Protection Unit
Circuit Breaker
Protection Unit
Enter J
Protection 1
Nr.
The information remains available for hours with dead relay.
- Value the current and power the has tripped. Using the "Trip Test" function lets you view the disabling/enabling the Trip.
- Value the current interrupted the LSIU has tripped.7 Information Menu
The Information Menu enables you view the data relating the protection unit and the type circuit-breaker.
Menu 4/5
Measures ▲
Settings
Device test
Enter J
Password Test 1/6
Enter status 1
0*** Auto Test
------------------------ Trip Test (disabled)
Enter password open
The menu shows the state the CB, the dialog module (COM module) the state the springs and the position the CB, and this submenu
you can make the open close.1 Information the trip and opening data
The PR123/DC unit saves all the information relating the type protection tripped, the opening data, the date and time.6.5.
■Indication for protection tripped.7. 050 092
Device E2B800/SP
Rated Curr.
- Value the voltage OV, have tripped.
Access view the opening data via the Historicals submenu the Measurements menu.02 ___
June 12, 2007 8:52:11:733
I1: 625A n
■Number openings due the protections and the TRIP tests. Using the Test" key
makes the release show all these data directly the display.
The percentage wear depends the number openings carried out the circuit-breaker and the absolutecurrent interrupted during
each them.
The prealarm message (wear 80%, "warning" LED lighting up) indicates that the wear has reached high value. No. The function only available with busbar current nil (use Vaux, PR030/B PR010/T).Thealarm message (100%
wear, "alarm" LED lighting up) indicates that necessary check the state contact wear.1 Test Menu table
Parameter Function Values Notes
CB status Open/Closed/Indefinite Indefinite case fault only
Auto Test Display test
Trip Test Enabled/Disabled
PR120/D-M
Module
State springs
Position CB
Open CB
Close CB
Loaded/Unloaded
Isolated/Withdrawn
PR120/K
Module
Input
Auto Test
ON
Zone
selectivity
Protection S
(status) Input
Force Output
Release Output
Protection G
(status) Input
Force Output
Release Output
ON/OFF
ON/OFF
13.13.5. With auxiliary
power supply, the information shown immediately the display without the need press the Test" key and remains displayed indefinitely
until you press the key. The following example the information provided:
Last Trip N.5. The data relating the last trips are stored the unit's memory.5.
73/108
.
The surfing path summarized the following table:
13. enabled, the circuit-breaker
is opened. G0000A03A
Device PR123/DC
Version LSIG
Normative IEC
Software 1.00
ESC
+ Enter J
Circuit Breake^ 1
Nr.
Model 3447
Apparatus Emax DC
Scale
Doc