ABB Softstartéry - opravy, náhradní díly (EN)

| Kategorie: Leták / Datasheet  | Tento dokument chci!

Vydal: ABB s.r.o, ELSYNN Autor: ABB ELSYnn

Strana 73 z 79







Poznámky redaktora
Set the parameter ByPass AC3. For set-up Torque Control during start and stop see separate manual sheet update manual. Set the parameters SOP1 SOP4. If wrong language was selected press Back for previous level. Press Store save the value and press Next continue. These commands are valid for the whole set-up. Press Yes the question “Are you sure?” 4. 5. 2. (table 1or 2) 10. (table 1or 2) 7. Set the parameter PST(B). Before taking the softstarter operation, don’t forget set the rated motor current and activate the required protections, warnings, input outputs etc. 12.only the board changed, the softstarter ready start. Set the parameter Ratio Ir. -. (table 1or 2) 8. Set the required display language. (table 2) 6. Follow the step step instruction below this set-up. (table 2) 9. the board changed, a programming this must done before the softstarter can taken operation. Every softstarter size has its own parameter values for the board according table (see next page) that must used. 1. Enter the menu Service settings using following path: Menu SETTINGS Service Settings New PCB and press Select 3. 11. Set the parameter Int ByPass. After pressing Next when the parameter PST(B) set, the programming complete. Switch the power supply (terminal 1and 2)