Set the parameter ByPass AC3. the board changed, a
programming this must done before the softstarter can taken operation.
5. Set the parameters SOP1 SOP4. Set the parameter Int ByPass. Set the required display language.
1. (table 1or 2)
10. Set the parameter PST(B). For set-up Torque Control during start and stop see separate manual sheet update
manual. Set the parameter Ratio Ir. Press Yes the question “Are you sure?”
4. If
wrong language was selected press Back for previous level.only the board changed, the softstarter ready start. Enter the menu Service settings using following path:
Menu SETTINGS Service Settings New PCB and press Select
3.
-. (table 2)
9. Switch the power supply (terminal 1and 2). Press Store save the value and press Next continue.
2. (table 1or 2)
8. After pressing Next when the parameter PST(B) set, the programming complete. Before taking the softstarter operation, don’t forget set the rated motor current and
activate the required protections, warnings, input outputs etc. (table 2)
6. Follow the step step instruction below this set-up.
12. These commands are valid for
the whole set-up. Every softstarter
size has its own parameter values for the board according table (see next page) that
must used. (table 1or 2)
7.