Poznámky redaktora
-. A person walking carpet can charged with fifteen thousand volt (15000V). Tools The need tools depends type softstarter. To able follow this instruction, you will need megger. Remove the plastic front cover (the example shows PST). Testing the thyristors -Step step Before disconnecting the cables mark them.ESD Warning -Please note! The life span electronics can affected damage caused electrostatic discharge. . This can happen charged tool person touches component. The tools are listed the instruction for how to change thyristors. Please look the correct instruction for the softstarter type you have. kindly ask you pay notice this, this vital point order to ensure the life span the product also after repair. Compare this with the fact that some sensitive components can destroyed when discharged much lower level (about 100V). Megger possible set 500V 3. Therefore very important that all tools and personnel are discharged touching an earthed point before the printed circuit board any the components are touched. Disconnect the power cables from the main terminals 1L1, 3L2, and 5L3 and the motor cables from terminals 2T1, 4T2 and 6T3 Disconnect all cables from the terminals 1to 20, the external keypad, and the PTC sensor and if used, the Field bus plug. 2