EN 62305-2 Protection Against Lightning Part Risk management provides procedure for the
evaluation risk for structure due lightning flashes earth.
The subject was extensively discussed and result 81X unequivocally determined great
majority (all delegates but FR,ES and PT) that:
– Standard 17-102 and 62305 Standards have the same scope;
– Standard 17-102 and 62305 Standards have conflicting requirements
– Standard 17-102 not product standard
Hereunder, according 135/02, the basis the decision meeting are presented by
specifically listing the principal conflicting clauses the two Standards.
EN 62305-4 Protection Against Lightning Part Electric and electronic Systems structures gives
the requirements for LEMP protection measures system (LPMS) for electrical and electronic systems
within structure, able reduce the risk permanent failures due lightning electromagnetic
impulse (LEMP).Specification main 17-102 standard requirements
in conflict with 62305 standard
1.
3
.
EN 62305-3 Protection Against Lightning Part Physical damage structures and life hazard gives
the requirements for lightning protection system (LPS) able reduce the risk physical damage to
structures and life hazard due lightning flashes the structure. The considered Standards
EN 62305
This standard consists coordinated parts,
(See 62305-1 Clause “Normative references”, page 15):
EN 62305-1 Protection Against Lightning Part General principles gives the general principles and
the basic criteria for protection structures against lightning irrespective technologies adopted
protection measures and their performances. Foreword
At its last meeting held Bruxelles 2009/09/02, CLC/TC81X considered the 134 decisions 35,
36, 37, and the compatibility Standard 17-102 with the CENELEC 62305 Standards, in
the aim to:
a) give the certified and authoritative interpretation 62305 standard;
b) evaluate whether 17-102 has conflicting requirements with 62305;
c) supply correct advice this matter for 135 meeting (November 2009). The same clauses
are reported the Annexes.