Refer Xtralis Design Guides
& Application Notes for sampled air pre-conditioning. English Russian language set.25% obs/ft)
Individual Alarm Delays seconds
Two Alarm Threshold Settings Either time GPI based
Display
• Alarm State Indicators Fault and Disabled Indicators
• Smoke Level Indicator Instant Fault Finder
• Reset, Disable and Test Controls Smoke and Flow AutoLearn Controls
Event Log
Up 18000 events, time and date stamped separate, non-volatile, logs for:
Smoke Level, Flow Level, Detector Status and Faults
AutoLearn Smoke Flow
• Automatically set acceptable alarm thresholds for both smoke and flow levels
• Minimum minutes, maximum days (default days)
• During AutoLearn thresholds are NOT changed from pre-set values
Warranty Period
2 years
Ordering Information:
VLF-250-00 VESDA VLF. European language set. (4.
When the Instant Fault Finder function is
activated, the Smoke DialTM
converts a
fault indicator, with the dial segment numbers
corresponding the faults listed below. International display labels
VIC-010 VESDAnet Interface Card, VIC-020 Multifunction Control Card (MCC)
VIC-030 Multifunction Control Card (MCC) with Monitored Powered Output (MPO)
VSP-005 Filter Cartridge
VSP-722 Aspirator for VESDA VLF-250
The contents this document are provided “as is” basis. NO/NC Contacts
Cable Access
3 (1. International display labels
VLF-250-02 VESDA VLF.) cable entries rear entry, top entry)
Cable Termination
Screw Terminals 0.)
Area Coverage
Up 250 (2,690 sq.625% obs/ft)
Fire Fire 0.xtralis.
Xtralis, the Xtralis logo, The Sooner You Know, VESDA-E, VESDA, ICAM, ECO, OSID, HeiTel, ADPRO, IntrusionTrace, LoiterTrace, ClientTrace,
SmokeTrace, XOa, XOh, iTrace, iCommand, iRespond, iCommission, iPIR, and FMST are trademarks and/or registered trademarks Xtralis and/or its
subsidiaries the United States and/or other countries.4 lbs)
IP Rating IP30
Mounting Upright, inverted horizontal
Operating Conditions*
Ambient: 0°C 39°C (32°F 103°F)*
Tested (EN54-20): -10°C 55°C (14°F 131°F)
Sampled Air**: -20°C 60°C (-4°F 140°F)
Humidity: 95% RH, non-condensing
Sampling Network
Maximum pipe lengths: (80 ft) (Max.025 20.025 2.00% obs/m (0.
www. holes per branch)
Sampling Hole Options: Pre-Engineered Option Maximum Pipe length in
accordance with Pipe Modelling Design Tool (ASPIRE™)
Air Inlet Pipe
Accepts both metric and American standard pipe sizes
Metric: (1.
This document subject copyright owned Xtralis. 07854_17 Part: 20293
VESDA VLF VLF-250
Approvals Compliance
Please refer the Product Guide for details
regarding compliant design, installation and
commissioning. The manufacturer reserves the right change designs specifications without obligation
and without further notice.com
UK and Europe +44 1442 242 330 D-A-CH +49 431 23284 The Americas 781 740 2223
Middle East +962 588 5622 Asia +86 5240 0077 Australia and New Zealand +61 9936 7000
.
** Sampled Air temperature shall reach Ambient Detector
temperature upon entry into Detector. Other brand names mentioned herein are for identification purposes only and may trademarks
of their respective holder(s). English Eastern Euro language set. representation warranty (either express implied) made the completeness,
accuracy reliability the contents this document.05 in.
* Product listed for use from 0°C 38°C (32°F 100°F). European language set.008 0.008 6.5 mm2 (30-12 AWG)
Interfaces
Shown Terminal Block Connections diagram, right, plus RS232 Programming Port.
Legend fault indicators:
1 Filter External Device/PSU
2 Aspirator Interface card
3 High flow Field wiring
4 Low flow AutoLearn Fail
5 n/a Detector failure
When the field service access door open,
the user has access the RESET ,
DISABLE Fire Test AutoLearn
and Instant Fault Finder functions.
Alarm Threshold Setting Range
Alert, Action 0. Except otherwise provided, all warranties, express implied, including without limitation any implied warranties of
merchantability and fitness for particular purpose are expressly excluded. holes)
2 (50 ft) per branch (Max.05 in. English display labels
VLF-250-01 VESDA VLF. You agree not copy, communicate the public, adapt, distribute, transfer, sell, modify or
publish any contents this document without the express prior written consent Xtralis. Your use this document does not constitute create licence any other right use the name and/or trademark and/
or label.2-2.) depending local codes and standards
Relay Outputs
3 changeover relays (Fire Action, Fault), Contacts rated VDC (max).
FIRE 2
FIRE 1
ALERT
ACTION
RESET
FAULT
DISABLE(D)
AUTOLEARN
FIRE 2
FIRE 1
ALERT
ACTION
RESET
FAULT
DISABLE(D)
AUTOLEARN
Fire relay
Doc.00% obs/m (0.) American Pipe: IPS in.Terminal Block Connections:
1 GPI
2 GPI
3 Display TX
4 Display RX
5 Display Common Ground
6 Display Power -
7 Display Power +
8 Power Return VDC
9 Power VDC
10 Power Return VDC
11 Power Out VDC
12 NC
13 Common
14 NO
15 NC
16 Common
17 NO
18 NC
19 Common
20 NO
From power
supply unit
To next detector
(if more than detector
per Power Supply Unit)
Fault relay
Action relay
Display:
The display provided the user includes a
Smoke DialTM
and alarm and status indicators. International display labels
VLF-250-05 VESDA VLF.
Specifications
Input Power
Voltage: 24V Nominal (18-30 DC)
Current VDC: 220 nominal, 295 alarm
Dimensions 256 183 (101
/16
in 71
/5
in 32
/3
in)
Weight Approx. no. ft. International display labels
VLF-250-04 VESDA VLF.
General Purpose Input (GPI) interface offers: Reset, Disable, Standby, Alarm set Alarm set 2
and External Input functions. English Asian language set