The use of innovations and new technologies at Hageris always customer-driven. Every year, Hager evaluatesthousands of its customer contacts, resulting in detailedknowledge of its customers’needs in order to workefficiently and successfully.
Poznámky redaktora
After additional five minutes without detection the lighting switched off.
Short press (less than 400 ms)
Connection parallel BLC presence detectors with constant light control not
permitted.
Technical data
Power supply
Connected load
Power consumption
Delay time
Brightness threshold value
Detection angle
Detection levels
Number zones
Number switching segments
Detection area desk level
Detection area floor level
Installation height for nominal detection areas
Number extension units
Extension unit cable length
Dimensions H)
Radio interference suppression
Operating temperature
BLC presence detector with constant light control order no.e. is
mounted exclusively ceilings, and monitors the area located below it, for example. The presence
detector switches the lighting only for long needed.
See short press. The constant light control
is designed that the user notices little possible.
· With mechanical push-button, distinction made between short press and a
long press.
Load remains switched during motion.5 times the setpoint. The presence detector switches the lighting when it
detects motion and the brightness below the set level. 10-1000 lux/symbol "0" initial activation only via extension unit
360°
6
80
320
approx. Never-
theless the brightness exceeds 1. when bright enough even
without lighting when there longer anyone present.
· presence detector mode the dimmed brightness value temporarily adopted the
brightness setpoint, long the lighting remains switched on. The delay time corresponds to
the value set the potentiometer,
but least minutes. motion detected now, the
lighting may switched again, depending the brightness situation. m
2. min.
Temporary deactivation the lighting control
If the presence detector switched the lighting off due sufficient extraneous light (e.
Notes:
· Each press re-starts the set delay time, but for least minutes.
Lighting switched off
for minutes.5 m
see BLC insert
max. For switch inserts the switch-off brightness (brightness setpoint) approx. daylight increases, the lighting dimmed switched off.
Monitored area light enough due to
switched-on lighting.
With motion the switch turned off
after the set delay time. m
approx. sec. After waiting period 10
minutes the lighting switched off regardless motion.
Load off Load on
Monitored area too dark:
Load remains switched during motion.
The lighting only switched off the presence detector does not detect any more
motion and the delay time has elapsed. due more daylight) twice the set
value.
The area evaluated expanded.
Delay time
The potentiometer "time" can used set the delay time; change operating mode
is indicated flashing the LED. When dimmer insert used, presence detector mode
the minimum brightness simultaneously used the setpoint which
the brightness held constant. the dimmer insert's
own non-temporary brightness memory changed, then BLC button must used
temporarily for saving the dimmer insert.
· Illuminated push-buttons must supplied with power via separate neutral
conductor.
· controller operation the lamps retain the dimmed brightness long the lighting
remains switched on. this,
switch the lighting again the extension unit within minute after switched off
automatically.
LED
flashes
Monitored area bright
enough:
Load remains off even
when motion detected. After that it
dims the lighting that the brightness held constant the setpoint that has been set
(constant light control).
BLC presence detector combination with BLC controller extension units. Detected
motions extend the delay time
to the time set the potentiometer.
brightness. The presence detector
switches the lighting off longer needed, i.
Installation location
· Ceiling mounting indoor areas.
Cooling light bulbs and air movements from,
for example, fans, heaters and open windows may
be detected and lead switching-on again.
During installation, not subject the sensor window the presence detector direct
sunlight; this could destroy the sensor.
Extension unit operation
For manual operation the presence detector, BLC extension unit (passive extension
unit) required combination with BLC button mechanical push-button (NO
contact).
Combination with BLC dimmer insert
The presence detector first switches the lighting maximal brightness. setting "Test"
Presence mode: approx.
LED
on
Monitored area bright
enough:
Load remains off even
when motion detected.
For more information,
see slide show-function
Load off Load on
Information regarding dimmer inserts
· After switching-on, constant light control performed.
See short press. sec. This makes
optimal adjustment possible without detaching the cover. The fact that the brightness exceeded indicated flashing the LED.T16
Function:
The BLC presence detector with constant light control responds heat motions caused
by persons, animals objects. the presence detector detects motion the next minutes,
then the switch-off time extended. expand the
detection field, the presence detector can combined with BLC controller extension
unit insert and connected the main device.
Control surface Load off Load on
Long press (longer than 400 ms) only for BLC dimmer inserts
Control surface
Test LED (brightness settings help)
LED
off
Monitored area too
dark:
Load switched on
when motion detected.
· The detection area should not limited furniture, pillars, etc.
· Each detected motion re-starts the delay time set the potentiometer.
Combination with BLC switch insert
The lighting always switched maximum brightness. The detection area should not limited furniture, pillars, etc.
Step operation: approx.
· Vibration-free installation, because movements the detector can also trigger a
switching operation
Sources interference
Do not install the direct vicinity heat source. When the brightness drops below
this value, the presence detector switches the lighting when motion is
detected. The lighting switched off
when one the following cases applies:
· The presence detector detects more motion and the set delay time has
elapsed. W
approx. also able evaluate
small motions (fine motor functions), such those that typically occur offices.g. 100 m
103 mm
according 55015
0 °C
Brightness threshold value
Minimum brightness the area being monitored.
Top, Bottom,
Full surface
or
mech. sec.
Settings
The cover can removed order adjust the delay time
(operating mode) and brightness threshold value. necessary limit detection area using
supplied push-on cover.
Notes:
· When BLC switch insert used, distinction made between short press and
a long press.
Increase (dim up) the brightness
to maximum brightness. When set marking the automatic initial
detection deactivated, switching only possible manually via the extension
units.
daylight), then you can switch the lighting control off manually.
The lighting now remains switched long the presence detector detects motion. As
daylight decreases, the lighting switched dimmed up. motion detected extension unit, this reported the main
device, and the connected load switched the brightness below the threshold
value the main device.
With motion the switch turned off
after the set delay time. The lighting control now active again. This means that dimming and changing the temporary brightness
setpoint not possible.
400 lux here. 170110
via BLC insert
depending BLC insert
approx. can used for switching and dimming the lighting
in offices and common areas.
push-button
The lighting switched max. Using with main device BLC
universal touch dimmer) BLC controller extension units possible evaluate even
large areas. minutes, because
the brightness sufficient even without lighting.
Brightness sensor
Delay time setting
Brightness setting
Test and status LEDs
(brightness settings help)
Fresnel lens
10s
10min
30min
time
Test
0
lux
Top or
Full surface
Bottom
Mechanical
push-button
The lighting switched to
minimum brightness, held for s
and then dimmed maximum
brightness.
Monitored area very bright with lighting and
extraneous light:
Load switches off after approx.
The lighting switched dimmed, depending the BLC insert used. Only after minutes without motion being
detected the slide show function ended automatically.
Mount brightness sensor the
side away from windows to
avoid the effects scattered light. min. you wish to
end the slide show function manually, switch the lighting again manually the
extension unit (for dimmer inserts the brightness before switching-off will set).g.
The lighting switched to
minimum brightness. min.
· the lighting was switched off via the extension unit, switching-on can performed
only via the extension unit the last brightness value
Slide show function
With BLC extension unit mechanical push-button (NOCs) possible switch
the lighting off selectively.
· Extension unit operation only possible there cover fitted the main device.
· The presence detector has adjusted the lighting the lowest dimming setting. expand the detection field, use BLC controller extension units. The lighting then dimmed minimum brightness most one minute.
Reduce (dim down) the
brightness minimum
brightness.test operation;
approx.
The lighting also switched off when there motion.
BLC presence detector
with constant light control
. The lighting switched off
when one the following cases applies:
· more motion detected and the set delay time has elapsed
· The brightness exceeds for least minutes (e. presence detector operation;
approx