BERKER Wiring accessories + Building automation catalogue 2012

| Kategorie: Katalog  | Tento dokument chci!

The use of innovations and new technologies at Hageris always customer-driven. Every year, Hager evaluatesthousands of its customer contacts, resulting in detailedknowledge of its customers’needs in order to workefficiently and successfully.

Vydal: HAGER ELECTRO s.r.o. Autor: EN HAGER

Strana 533 z 616

Vámi hledaný text obsahuje tato stránku dokumentu který není autorem určen k veřejnému šíření.







Poznámky redaktora
min. Top, Bottom, Full surface or mech. This means that dimming and changing the temporary brightness setpoint not possible. This makes optimal adjustment possible without detaching the cover. · Each detected motion re-starts the delay time set the potentiometer. Never- theless the brightness exceeds 1. The detection area should not limited furniture, pillars, etc. BLC presence detector with constant light control . · controller operation the lamps retain the dimmed brightness long the lighting remains switched on. sec. Combination with BLC switch insert The lighting always switched maximum brightness. min. when bright enough even without lighting when there longer anyone present. m approx. sec. W approx. brightness. · Vibration-free installation, because movements the detector can also trigger a switching operation Sources interference Do not install the direct vicinity heat source. The lighting switched off when one the following cases applies: · The presence detector detects more motion and the set delay time has elapsed. BLC presence detector combination with BLC controller extension units. The presence detector switches the lighting when it detects motion and the brightness below the set level. · The detection area should not limited furniture, pillars, etc. Control surface Load off Load on Long press (longer than 400 ms) only for BLC dimmer inserts Control surface Test LED (brightness settings help) LED off Monitored area too dark: Load switched on when motion detected. The lighting then dimmed minimum brightness most one minute. expand the detection field, the presence detector can combined with BLC controller extension unit insert and connected the main device. due more daylight) twice the set value. Mount brightness sensor the side away from windows to avoid the effects scattered light. Short press (less than 400 ms) Connection parallel BLC presence detectors with constant light control not permitted.5 times the setpoint. The fact that the brightness exceeded indicated flashing the LED. Notes: · Each press re-starts the set delay time, but for least minutes. 400 lux here. necessary limit detection area using supplied push-on cover. Load remains switched during motion. Settings The cover can removed order adjust the delay time (operating mode) and brightness threshold value. · presence detector mode the dimmed brightness value temporarily adopted the brightness setpoint, long the lighting remains switched on.T16 Function: The BLC presence detector with constant light control responds heat motions caused by persons, animals objects.e. Extension unit operation For manual operation the presence detector, BLC extension unit (passive extension unit) required combination with BLC button mechanical push-button (NO contact). presence detector operation; approx. See short press.5 m see BLC insert max. The presence detector switches the lighting only for long needed. 10-1000 lux/symbol "0" initial activation only via extension unit 360° 6 80 320 approx. Combination with BLC dimmer insert The presence detector first switches the lighting maximal brightness. the dimmer insert's own non-temporary brightness memory changed, then BLC button must used temporarily for saving the dimmer insert. Lighting switched off for minutes. · With mechanical push-button, distinction made between short press and a long press. sec. Step operation: approx. also able evaluate small motions (fine motor functions), such those that typically occur offices. The lighting only switched off the presence detector does not detect any more motion and the delay time has elapsed. As daylight decreases, the lighting switched dimmed up. Detected motions extend the delay time to the time set the potentiometer. Delay time The potentiometer "time" can used set the delay time; change operating mode is indicated flashing the LED. Installation location · Ceiling mounting indoor areas. When set marking the automatic initial detection deactivated, switching only possible manually via the extension units. daylight increases, the lighting dimmed switched off. During installation, not subject the sensor window the presence detector direct sunlight; this could destroy the sensor. The lighting switched to minimum brightness. m 2.test operation; approx. setting "Test" Presence mode: approx. · The presence detector has adjusted the lighting the lowest dimming setting. The lighting switched dimmed, depending the BLC insert used. The presence detector switches the lighting off longer needed, i. 170110 via BLC insert depending BLC insert approx. For more information, see slide show-function Load off Load on Information regarding dimmer inserts · After switching-on, constant light control performed. LED on Monitored area bright enough: Load remains off even when motion detected. · the lighting was switched off via the extension unit, switching-on can performed only via the extension unit the last brightness value Slide show function With BLC extension unit mechanical push-button (NOCs) possible switch the lighting off selectively. can used for switching and dimming the lighting in offices and common areas. minutes, because the brightness sufficient even without lighting. When the brightness drops below this value, the presence detector switches the lighting when motion is detected. Temporary deactivation the lighting control If the presence detector switched the lighting off due sufficient extraneous light (e. you wish to end the slide show function manually, switch the lighting again manually the extension unit (for dimmer inserts the brightness before switching-off will set). After that it dims the lighting that the brightness held constant the setpoint that has been set (constant light control). 100 m 103 mm according 55015 0 °C Brightness threshold value Minimum brightness the area being monitored.g. Reduce (dim down) the brightness minimum brightness. The lighting control now active again. With motion the switch turned off after the set delay time.g. After additional five minutes without detection the lighting switched off. Only after minutes without motion being detected the slide show function ended automatically. The lighting also switched off when there motion. After waiting period 10 minutes the lighting switched off regardless motion. When dimmer insert used, presence detector mode the minimum brightness simultaneously used the setpoint which the brightness held constant. Brightness sensor Delay time setting Brightness setting Test and status LEDs (brightness settings help) Fresnel lens 10s 10min 30min time Test 0 lux Top or Full surface Bottom Mechanical push-button The lighting switched to minimum brightness, held for s and then dimmed maximum brightness. Using with main device BLC universal touch dimmer) BLC controller extension units possible evaluate even large areas. Cooling light bulbs and air movements from, for example, fans, heaters and open windows may be detected and lead switching-on again. Technical data Power supply Connected load Power consumption Delay time Brightness threshold value Detection angle Detection levels Number zones Number switching segments Detection area desk level Detection area floor level Installation height for nominal detection areas Number extension units Extension unit cable length Dimensions H) Radio interference suppression Operating temperature BLC presence detector with constant light control order no. Load off Load on Monitored area too dark: Load remains switched during motion. The area evaluated expanded. Monitored area light enough due to switched-on lighting. The delay time corresponds to the value set the potentiometer, but least minutes. The lighting switched off when one the following cases applies: · more motion detected and the set delay time has elapsed · The brightness exceeds for least minutes (e. Monitored area very bright with lighting and extraneous light: Load switches off after approx. See short press. is mounted exclusively ceilings, and monitors the area located below it, for example. min. daylight), then you can switch the lighting control off manually. this, switch the lighting again the extension unit within minute after switched off automatically. LED flashes Monitored area bright enough: Load remains off even when motion detected. The lighting now remains switched long the presence detector detects motion. Notes: · When BLC switch insert used, distinction made between short press and a long press. The constant light control is designed that the user notices little possible. For switch inserts the switch-off brightness (brightness setpoint) approx. · Extension unit operation only possible there cover fitted the main device. expand the detection field, use BLC controller extension units. Increase (dim up) the brightness to maximum brightness. the presence detector detects motion the next minutes, then the switch-off time extended. With motion the switch turned off after the set delay time. push-button The lighting switched max. motion detected extension unit, this reported the main device, and the connected load switched the brightness below the threshold value the main device. · Illuminated push-buttons must supplied with power via separate neutral conductor. motion detected now, the lighting may switched again, depending the brightness situation