MECHANICAL CHECK
RESET THE CIRCUIT-BREAKERS OPERATING MECHANISM SPRINGS AND PERFORM THE FOLLOWING OPERATIONS:
1. REARME LOS MUELLES
DEL MANDO DEL INTERRUPTOR "B", COMPRUEBE QUE ÉSTE PERMANEZCA CERRADO LUEGO ÁBRALO. REARME LOS MUELLES
DEL MANDO DEL INTERRUPTOR "A", COMPRUEBE QUE ÉSTE PERMANEZCA CERRADO LUEGO ÁBRALO. TERMINE DEI TEST VERIFICARE REGOLAZIONI BLOCCAGGIO DEI TIRANTI. CERRAR INTERRUPTOR CONTROLAR CHE LOS INTERRUPTORES "A" "B" PUEDAN CERRARSE. RIARMARE LE
MOLLE DEL COMANDO DELL' INTERRUTTORE "A" VERIFICANDO CHE STESSO RESTI CHIUSO, QUINDI APRIRE L'INTERRUTTORE
"A".
2. REARME LOS MUELLES
DEL MANDO DEL INTERRUPTOR "C", COMPRUEBE QUE ÉSTE PERMANEZCA CERRADO LUEGO ÁBRALO. CHIUDERE L'INTERRUTTORE "B" CONTROLLARE CHE GLI INTERRUTTORI "A" "C" NON POSSANO ESSERE CHIUSI. RÉARMER LES
RESSORTS COMMANDE DISJONCTEUR "A" VÉRIFIANT QUE DERNIER RESTE FERMÉ, PUIS OUVRIR DISJONCTEUR
"A".
CONTROL MECÁNICO
RESTABLECER LOS RESORTES LOS MANDOS LOS INTERRUPTORES EFECTUAR LAS SIGUIENTES OPERACIONES:
1.
3.
3. DER LEISTUNGSSCHALTER "C" SCHLIESSEN UND SICHERSTELLEN, DASS DIE LEISTUNGSSCHALTER "A" UND "B" NICHT
GESCHLOSSEN WERDEN KÖNNEN.
3. RIARMARE LE
MOLLE DEL COMANDO DELL' INTERRUTTORE "C" VERIFICANDO CHE STESSO RESTI CHIUSO, QUINDI APRIRE L'INTERRUTTORE
"C". RESET THE SPRINGS
ON THE "B" CIRCUIT-BREAKER CONTROL, MAKING SURE THAT REMAINS CLOSED, THEN OPEN THE "B" CIRCUIT-BREAKER. RÉPÉTER TEST FOIS. REPEAT THE TEST THREE TIMES, THEN CHECK THE ADJUSTMENTS AND THE FASTNESS THE TIE-RODS. FERMER DISJONCTEUR "A" CONTROLER QUE LES DISJONCTEURS "B" "C" PEUT PAS ETRE FERME. RIARMARE LE
MOLLE DEL COMANDO DELL' INTERRUTTORE "B" VERIFICANDO CHE STESSO RESTI CHIUSO, QUINDI APRIRE L'INTERRUTTORE
"B".
2.
4. RÉARMER LES
RESSORTS COMMANDE DISJONCTEUR "B" VÉRIFIANT QUE DERNIER RESTE FERMÉ, PUIS OUVRIR DISJONCTEUR
"B".: +39 035 395.
3. CERRAR INTERRUPTOR "B", CONTROLAR CHE LOS INTERRUPTORES "A" "C" PUEDAN CERRARSE.
2. CLOSE CIRCUIT-BREAKER "C" AND MAKE SURE THAT THE CIRCUIT-BREAKERS "A" AND "B" CANNOT CLOSED. REPITA PRUEBA OTRAS TRES VECES LUEGO, COMPRUEBE LOS AJUSTES BLOQUEO LOS TIRANTES.p. CHIUDERE L'INTERRUTTORE "A" CONTROLLARE CHE GLI INTERRUTTORI "B" "C" NON POSSANO ESSERE CHIUSI.
4.
REGLAGE
REARMER LES RESSORTS DES COMMANDES DES DISJONCTEURS EFFECTUER LES OPERATIONS SUIVANTES:
1.
4. FERMER DISJONCTEUR "B" CONTROLER QUE LES DISJONCTEURS "A" "C" PEUT PAS ETRE FERME. ANSCHLIESSEND DEN LEISTUNGSSCHALTER "B" ÖFFNEN.306-433
http://www.ZD
CONTROLLO MECCANICO
RIARMARE MOLLE DEI COMANDI DEGLI INTERRUTTORI ESEGUIRE SEGUENTI OPERAZIONI:
1. RIPETERE TEST PER VOLTE.
EINSTELLUNG
DIE FEDERN DER ANTRIEBE DER LEISTUNGSSCHALTER WIEDER SPANNEN UND FOLGENDE SCHALTUNGEN AUSFÜHREN:
1.
2.
2.
Via Baioni, 35
24123 Bergamo Italy
Tel.A. RÉARMER LES
RESSORTS COMMANDE DISJONCTEUR "C" VÉRIFIANT QUE DERNIER RESTE FERMÉ, PUIS OUVRIR DISJONCTEUR
"C".
4.com
. CLOSE CIRCUIT-BREAKER "B" AND MAKE SURE THAT THE CIRCUIT-BREAKERS "A" AND "C" CANNOT CLOSED. ANSCHLIESSEND DEN LEISTUNGSSCHALTER "C" ÖFFNEN.abb.
4. DER LEISTUNGSSCHALTER "A" SCHLIESSEN UND SICHERSTELLEN, DASS DIE LEISTUNGSSCHALTER "B" UND "C" NICHT
GESCHLOSSEN WERDEN KÖNNEN.
A i
M m
ABB SACE S. RESET THE SPRINGS
ON THE "C" CIRCUIT-BREAKER CONTROL, MAKING SURE THAT REMAINS CLOSED, THEN OPEN THE "C" CIRCUIT-BREAKER. FEDERN DES ANTRIEBS VOM LEISTUNGSSCHALTER "B" ZURÜCKSTELLEN UND ÜBERPRÜFEN,
DASS DER LEISTUNGSSCHALTER GESCHLOSSEN BLEIBT. DER LEISTUNGSSCHALTER "B" SCHLIESSEN UND SICHERSTELLEN, DASS DIE LEISTUNGSSCHALTER "A" UND "C" NICHT
GESCHLOSSEN WERDEN KÖNNEN.111 Telefax: +39 035 395. FEDERN DES ANTRIEBS VOM LEISTUNGSSCHALTER "C" ZURÜCKSTELLEN UND ÜBERPRÜFEN,
DASS DER LEISTUNGSSCHALTER GESCHLOSSEN BLEIBT. FERMER DISJONCTEUR "C" CONTROLER QUE LES DISJONCTEURS "A" "B" PEUT PAS ETRE FERME. CERRAR INTERRUPTOR "A" CONTROLAR CHE LOS INTERRUPTORES "B" "C" PUEDAN CERRARSE. ANSCHLIESSEND DEN LEISTUNGSSCHALTER "A" ÖFFNEN.
3. CLOSE CIRCUIT-BREAKER "A" AND MAKE SURE THAT THE CIRCUIT-BREAKERS "B" AND "C" CANNOT CLOSED. RESET THE SPRINGS
ON THE "A" CIRCUIT-BREAKER CONTROL, MAKING SURE THAT REMAINS CLOSED, THEN OPEN THE "A" CIRCUIT-BREAKER. FEDERN DES ANTRIEBS VOM LEISTUNGSSCHALTER "A" ZURÜCKSTELLEN UND ÜBERPRÜFEN,
DASS DER LEISTUNGSSCHALTER GESCHLOSSEN BLEIBT. TEST DREI MAL WIEDERHOLEN