aux YU)
The undervoltage releases can fitted with contact (by choise, normally closed open) for signalling undervoltage energized for remote
signalling the state the undervoltage release.3 250 0.
Power supply: 24-30 AC/DC
220-240 AC/DC__________
_____________________________________110-130 AC/DC__________
Reference figure the electrical circuit diagrams: S51 (14)
A ilia ts
Auxiliary contacts installed the circuit-breaker are available enable indication the circuit-breaker's status. the electrical circuit diagrams: /1^10 (21-22)
b) Electrical signalling for circuit-breaker connected/test isolated/disconnected
In addition mechanical signalling the position the circuit-breaker, possible have electrical signalling means auxiliary
contacts which are installed the fixed part.
Reference Fig.
Reference figure the electrical circuit diagrams: UI/N
Model 2234 Apparatus Scale
L 2778
Doc-No- 1SDH000460R0002
Page No.
Only available for circuit-breakers withdrawable versions for installing the fixed part.
The basic configuration described above can modified the user indicate normally open normally closed repositioning the faston
connector the microswitch. With this accessory, you can reset the mechanical indicator with electronic
relay using remote control and this enables the circuit-breaker reset.llin s
The following signals are available following tripping the overcurrent release:
a) echanical trip signalling for overcurrent releases
This enables visual signalling the operating mechanism pushing the trip pushbutton when the circuit-breaker has been opened following
tripping overcurrent release.
The auxiliary contacts can have the following configurations:
- break/make contacts for PR121 normally open normally closed)
- break/make contacts for PR122/ PR123 normally open normally closed for the release)
- break/make contacts for PR121 normally open normally closed);
- break/make contacts for PR122/ PR123 normally open normally closed for the release)
- supplementary break/make contacts which can mounted outside the circuit-breaker. When contacts for PR122/ PR123 are required, zone selectivity and the PR120/K module are not available.
c) Coil for resetting the echanical release trip indicator
This enables visual signalling the operating mechanism (mechanical) and remotely (electrically means changeover switch) the circuit-
breaker being opened following trip the overcurrent releases. is
supplied request. The circuit-breaker can only closed again putting the pushbutton back into its normal position included in
the standard configuration.
Un max max ç
125 0.3
250 0.
The auxiliary contacts can have the following configurations:
- contacts; group consisting connected signalling contacts, disconnected signalling contacts and test position signalling contact (main
contacts isolated, but sliding contacts connected)
- contacts; group consisting connected signalling contacts, disconnected signalling contacts and test position signalling contacts (main
contacts isolated, but sliding contacts connected).
Reference figure the electrical circuit diagrams: S51 (13).
26/158
.15 ms
The versions available are:
a) Electrical signalling for circuit-breaker open/closed
It possible have electrical signalling the circuit-breaker status (open/closed) auxiliary contacts.
b) lectrical and echanical trip signalling for overcurrent releases
This enables visual signalling the operating mechanism (mechanical) and remotely (electrically means changeover switch) the circuit-
breaker being opened following trip the overcurrent releases.
Reference figure the electrical circuit diagrams: S51 (13).
Reference figure the electrical circuit diagrams: S75I (31-32) S75T (31-32) S75E (31-32)
c llin rin loaded
This consists microswitch which allows remote signalling the state the circuit-breaker operating mechanism closing springs. reset the circuit-breaker, necessary reset the mechanical indicator
pushbutton. The contact
is always supplied with the spring loading geared motor.
Reference figure the electrical circuit diagrams: (12)
T tio rs
a) Current sensor for the neutral conductor outside the circuit-breaker
The sensor allows neutral protection means connection the overcurrent release and available only for three-pole circuit-breakers. special version the auxiliary
contacts also available (gold plated contacts) for rated voltage under (digital signal).
Reference figure the electrical circuit diagrams: S33 M/2 (11)
d) ontact for signalling undervoltage release energized (C