After circuit-breaker closing, the geared motor immediately
sees reloading the closing springs.lta (D)
The undervoltage release can combined with electronic time-delay device for installing outside the circuit-breaker, which enables delay
in the tripping the release with preset, adjustable times.
When there power supply during maintenance work, the closing springs can still loaded manually (by means the special lever on
the operating mechanism).)
It always supplied with limit contacts and microswitch for signalling closing springs loaded.
25/158
.
Reference figure the electrical circuit diagrams: (1)
Model 2234 Apparatus Scale
L 2778
Doc-Na 1SDH000460R0002
Page No.
The time-delay device has combined with undervoltage release with the same voltage the time-delay device.5-2-3 s
G tic rin )
This automatically loads the circuit-breaker operating mechanism closing springs.
The characteristics the time-delay device are:
Power supply (D): 24-30 AC/DC
48 AC/DC
60 AC/DC
110-127 AC/DC
____________________________________ 220-250 AC/DC
Adjustable opening time (YU D): 0.5-1-1.
Reference figures the electrical circuit diagrams: (7). The use the delayed undervoltage release recommended when the power supply
network the release can subject power cuts short-lived voltage drops, order avoid trips.
When not supplied, circuit-breaker closing prevented.
Power supply 24-30 AC/DC
48-60 AC/DC
100-130 AC/DC
220-250 AC/DC
Operating limits: (CEI 60947-Standards)
Inrush power consumption (Ps): 500 W
AC 500 VA
Rated power (Pn): 200 W
AC 200 VA
Inrush time 0.2 s
Loading time: 4-5 s
Insulation voltage 2500 (for min