4. Select "Install" and press "ENTER"
9. Check for the absence configuration errors.1 Installation
To complete the procedure for installing PR123/DC unit, follow the steps below:
1. Select "Circuit-breaker"
6.
For the default password see par. therefore always possible
to switch from "READ" "EDIT".4. 13.
Disabling the Password.2 Uninstalling
To complete the procedure for uninstalling PR123/DC unit, follow the steps below:
1. Enter the unit's "Settings" menu
5. Power the unit ONLY from the PR030/B
3.
13.g.13. Input the password
6. The remove the connector, proceed indicated the figure alongside. Select "Uninstall" and press "ENTER"
7. there are other errors, the display will show the message Configuration (configuration error) accompanied the yellow
LED coming permanently (warning)
4.
Note that ABB SACE defines each possible setting according the content the paragraph the default parameters (see par.
Model 7
A pparatus Emax DC
S cale
D oc-N 1SDH000635R0002
Page No.6.
If the password wrong, the message
Wrong password
appears and remains until the ESC key pressed (or until interval seconds has elapsed). When the red led flashes and off and the message Installation (installation error) displayed, remove the PR030/B
10.3. The data question are then transmitted the new PR123/DC unit installed
on the same circuit-breaker. Remove the PR123/DC unit from the circuit-breaker
9..4.
13.
To enter new password, select the "New Password" item the "Settings/System" menu. 13.3. type circuit-breaker, Rating Plug size. Remove the PR030/B
8. Power the relay from any other source
11.4 Initial settings
If the PR123/DC supplied ready installed the circuit-breaker, ABB SACE set all the variables referring the circuit-breaker or
the specific application correctly (e. The values attributable the password from 0000 9999. After entering the fourth figure, check the password you have entered.5 Password management
Specify password? [0***]
To enter "EDIT" mode necessary enter four-figure numerical password.6 Replacing electronic release
13.. When the PR120/V module installed, user must properly set
the rated voltage.
It not strictly necessary complete the uninstalling procedure, but this enables the parameters relating the circuit-breaker, such contact
wear and others, saved, otherwise these data would lost.
By setting the value the password [0000] (on the "Unit configuration" menu) the password prom disabled. Select "Circuit-breaker"
4. Input the password
8. Select "Unit installation"
5.
Select the value the first figure between '0' and '9' means the and keys and press confirm the figure and then move enter
the next one.3.3.4).3. Enter the unit's "Settings" menu
3.6.
61/108
. With the circuit-breaker open and/or isolated power the unit from the PR030/B
2.). With the circuit-breaker open and preferably isolated, install the protection unit the circuit-breaker
2. Select "Unit installation"
7.
13.
It also possible interrupt the password entry procedure pressing the ESC key. the password correct, you from the "READ" state
to the "EDIT" state.
Apart from this, absolutely indispensable for the user modify the password and carefully define each modifiable
parameter, before putting the PR123/DC into service.
Vice versa, the PR123/DC supplied separately, will the user set all the necessary parameters correctly