(table 2)
9.
12. Set the parameter Int ByPass. Every softstarter
size has its own parameter values for the board according table that must used.
Follow the step step instruction below this set-up. Set the required display language. These commands are valid for
the whole set-up. Press Yes the question “Are you sure?”
4. For set-up Torque Control during start and stop see separate manual sheet update
manual.
11. Enter the menu Service settings using following path:
Menu SETTINGS Service Settings New PCB and press Select
3. the board changed, a
programming this must done before the softstarter can taken operation. Switch the power supply (terminal 1and 2). (table 1or 2)
10. If
wrong language was selected press Back for previous level. (table 1or 2)
8. Set the parameter ByPass AC3.Configuration the LVboard
If only the board changed, the softstarter ready start. (table 1or 2)
7. Set the parameter PST(B).
-.
5. Before taking the softstarter operation, don’t forget set the rated motor current and
activate the required protections, warnings, input outputs etc.
1. (table 2)
6. After pressing Next when the parameter PST(B) set, the programming complete. Set the parameters SOP1 SOP4.
2. Set the parameter Ratio Ir. Press Store save the value and press Next continue