Poznámky redaktora
the board changed, a programming this must done before the softstarter can taken operation. Set the parameters SOP1 SOP4. Set the required display language. Switch the power supply (terminal 1and 2).Configuration the LVboard If only the board changed, the softstarter ready start. Follow the step step instruction below this set-up. 2. -. (table 1or 2) 10. Set the parameter Int ByPass. (table 2) 6. These commands are valid for the whole set-up. 12. Enter the menu Service settings using following path: Menu SETTINGS Service Settings New PCB and press Select 3. Press Yes the question “Are you sure?” 4. (table 1or 2) 8. For set-up Torque Control during start and stop see separate manual sheet update manual. Set the parameter ByPass AC3. Every softstarter size has its own parameter values for the board according table that must used. 1. Press Store save the value and press Next continue. 11. Set the parameter Ratio Ir. (table 1or 2) 7. Before taking the softstarter operation, don’t forget set the rated motor current and activate the required protections, warnings, input outputs etc. After pressing Next when the parameter PST(B) set, the programming complete. (table 2) 9. If wrong language was selected press Back for previous level. 5. Set the parameter PST(B)