ABB Softstartéry - opravy, náhradní díly (EN)

| Kategorie: Leták / Datasheet  | Tento dokument chci!

Vydal: ABB s.r.o, ELSYNN Autor: ABB ELSYnn

Strana 63 z 79







Poznámky redaktora
Set the parameter ByPass AC3. 11. For set-up Torque Control during start and stop see separate manual sheet update manual. Set the parameter PST(B). 2. Every softstarter size has its own parameter values for the board according table that must used. Press Store save the value and press Next continue. Set the required display language. Set the parameter Ratio Ir. Follow the step step instruction below this set-up. Set the parameter Int ByPass. (table 1or 2) 7.Configuration the LVboard If only the board changed, the softstarter ready start. (table 1or 2) 8. Set the parameters SOP1 SOP4. 12. Switch the power supply (terminal 1and 2). After pressing Next when the parameter PST(B) set, the programming complete. Before taking the softstarter operation, don’t forget set the rated motor current and activate the required protections, warnings, input outputs etc. If wrong language was selected press Back for previous level. 1. Press Yes the question “Are you sure?” 4. 5. (table 1or 2) 10. (table 2) 6. These commands are valid for the whole set-up. the board changed, a programming this must done before the softstarter can taken operation. Enter the menu Service settings using following path: Menu SETTINGS Service Settings New PCB and press Select 3. (table 2) 9. -