ABB Softstartéry - opravy, náhradní díly (EN)

| Kategorie: Leták / Datasheet  | Tento dokument chci!

Vydal: ABB s.r.o, ELSYNN Autor: ABB ELSYnn

Strana 63 z 79







Poznámky redaktora
(table 1or 2) 7. Before taking the softstarter operation, don’t forget set the rated motor current and activate the required protections, warnings, input outputs etc. 1. Set the parameter Int ByPass. 11. (table 1or 2) 10. After pressing Next when the parameter PST(B) set, the programming complete. For set-up Torque Control during start and stop see separate manual sheet update manual. Press Yes the question “Are you sure?” 4. 12. Enter the menu Service settings using following path: Menu SETTINGS Service Settings New PCB and press Select 3. If wrong language was selected press Back for previous level. (table 2) 9. Press Store save the value and press Next continue. -. Set the parameter PST(B). Switch the power supply (terminal 1and 2). (table 1or 2) 8. Every softstarter size has its own parameter values for the board according table that must used. Set the required display language. Set the parameter Ratio Ir. These commands are valid for the whole set-up. Set the parameter ByPass AC3. Follow the step step instruction below this set-up. 5. 2. Set the parameters SOP1 SOP4.Configuration the LVboard If only the board changed, the softstarter ready start. (table 2) 6. the board changed, a programming this must done before the softstarter can taken operation