Poznámky redaktora
Enter the menu Service settings using following path: Menu SETTINGS Service Settings New PCB and press Select 3. the board changed, a programming this must done before the softstarter can taken operation. Before taking the softstarter operation, don’t forget set the rated motor current and activate the required protections, warnings, input outputs etc. These commands are valid for the whole set-up. (table 1or 2) 10. (table 2) 6. 5. -. Follow the step step instruction below this set-up. Press Yes the question “Are you sure?” 4. For set-up Torque Control during start and stop see separate manual sheet update manual. Set the parameter PST(B). Set the parameter Int ByPass. Set the required display language. Set the parameter ByPass AC3. Set the parameter Ratio Ir. (table 1or 2) 8. 1. 11. Press Store save the value and press Next continue. (table 2) 9. Set the parameters SOP1 SOP4. Switch the power supply (terminal 1and 2). 12. After pressing Next when the parameter PST(B) set, the programming complete. Every softstarter size has its own parameter values for the board according table that must used. 2. If wrong language was selected press Back for previous level. (table 1or 2) 7.Configuration the LVboard If only the board changed, the softstarter ready start