For upgrade Torque Control is important check the connection the current transformer (see fig below). The resistance of the current transformer are between 0,2-6 ohm. 19. 17. 21. the two cables each current transformer are black use multimeter to detect the right connection.16. 20. Black cable White cable White side PSTB Black side Black cable White cable -. Mount the new HV-Board with the five screws. careful how you connect the cables from the thyristors. Mount the cables from the thyristors and fans the HV-Board. Mount the cables from the thermal switch and current transformers the LV-Board. Change the position the cables the current transformers obtain correct position necessary. Be careful how you connect the cables from the current transformers (correct phase sequence). 18