For upgrade Torque Control is important check the connection the current transformer (see fig below). The resistance of the current transformer are between 0,2-6 ohm. Change the position the cables the current transformers obtain correct position necessary. 19. 21. 17. careful how you connect the cables from the thyristors. the two cables each current transformer are black use multimeter to detect the right connection. Be careful how you connect the cables from the current transformers (correct phase sequence). Black cable White cable White side PSTB Black side Black cable White cable -. 20. 18.16. Mount the cables from the thyristors and fans the HV-Board. Mount the cables from the thermal switch and current transformers the LV-Board. Mount the new HV-Board with the five screws