7. Disconnect the cables the LV-Board from the thermal switch and current transformers. 6. Don’t lose the connector between HV-Board and LV- Board. Disconnect all cables from the terminals 1to 20, external keypad, PTC sensor and the Fieldbus plug.Step step 1. Mark the cables from the thyristors with L1, and L3. 10. Disconnect the cables the HV-Board from the thyristors and fans. Discharge the tools and yourselfby touching earth (if you are not earthed). 9. 2. Remove the five screws. 3. Remove the front cover (four screws). Remove the old HV-Board. Before disconnecting the cables mark them. 5. 4. -. Mark the cables from the current transformers with CT1, CT2 and CT3. 8. Remove the six screws. Disconnect the cables from terminals 1L1, 3L2, and 5L3 (main voltage)