Poznámky redaktora
2. (table 1or 2) 7. Set the parameter Int ByPass. (table 1or 2) 8. 11. Set the parameter ByPass AC3. Press Store save the value and press Next continue. (table 2) 9. 1. After pressing Next when the parameter PST(B) set, the programming complete. Press Yes the question “Are you sure?” 4. Follow the step step instruction below this set-up. If wrong language was selected press Back for previous level. These commands are valid for the whole set-up. 12. -. For set-up Torque Control during start and stop see separate manual sheet update manual. Set the parameter PST(B). 5. Every softstarter size has its own parameter values for the HMI Module according table 1or 2 that must used. (table 1or 2) 10. Set the parameters SOP1 SOP4.Configuration the HMI Module A programming the HMI Module must done before the softstarter can taken operation. Enter the menu Service settings using following path: Menu SETTINGS Service Settings New PCB and press Select 3. Before taking the softstarter operation, don’t forget set the rated motor current and activate the required protections, warnings, input outputs etc. Set the parameter Ratio Ir. (table 2) 6. Switch the power supply (terminal 1and 2). Set the required display language