Poznámky redaktora
For set-up Torque Control during start and stop see separate manual sheet update manual. Set the parameter ByPass AC3. -. Switch the power supply (terminal 1and 2). 11. (table 2) 9. Press Store save the value and press Next continue. Enter the menu Service settings using following path: Menu SETTINGS Service Settings New PCB and press Select 3. Every softstarter size has its own parameter values for the HMI Module according table 1or 2 that must used. Follow the step step instruction below this set-up. 1. Set the parameter Int ByPass. (table 1or 2) 10. (table 1or 2) 8. Before taking the softstarter operation, don’t forget set the rated motor current and activate the required protections, warnings, input outputs etc. Set the required display language. 2. Set the parameter PST(B). (table 1or 2) 7. 12. 5. After pressing Next when the parameter PST(B) set, the programming complete. Press Yes the question “Are you sure?” 4. (table 2) 6. Set the parameter Ratio Ir. Set the parameters SOP1 SOP4. If wrong language was selected press Back for previous level.Configuration the HMI Module A programming the HMI Module must done before the softstarter can taken operation. These commands are valid for the whole set-up