ABB Softstartéry - opravy, náhradní díly (EN)

| Kategorie: Leták / Datasheet  | Tento dokument chci!

Vydal: ABB s.r.o, ELSYNN Autor: ABB ELSYnn

Strana 23 z 79







Poznámky redaktora
Step step.... ♦Clean the contact surface the heat sink and modules with Ethanol.MCC162 3,0 5,0 2 SKKT210.SKKT172 MCC132..SKKT92 MCC26. ♦Disconnect all cable from the terminals.SKKT330 MCC225. ♦Remove the front cover. ♦Mount the new thyristors (Use the torque the table)... ♦Disconnect the electrical connection the thyristors. ♦Mount the electrical connection the thyristors.. ♦Discharge the tools and yourselfby touching earth.MCC312 3,0 9,0 3 SKKT500 MCC500 3,0Nm 12,0 4 -. Use lint-free cloth (paper linen cloth) ♦A very thin layer ofheat transfer compound shall put the contact surfaces of the modules with lint-free cloth.. ♦Mount the front cover. ♦Disconnect the voltage from terminals 1L1, 3L2, and 5L3 (main supply).. ♦Connect the voltage and the other cable. Ready for start!! Picture Picture Picture Picture 4 Semikron Thyristor IXYS Mounting torque Terminal connection torque Picture SKKT27..MCC95 3,0 3,0 1 SKKT132. ♦Disconnect the thyristors.. Too much compound between module and heat sink will give bad thermal conduction and cause risk overheating the thyristors.