Poznámky redaktora
The LEDs for phases (orS) andL3 (or remain off.GEN-SET PROBLEM DESCRIPTION POSSIBLE CAUSES The front selector does not start the generator - Wiring error. Make certain that you are usingthe correct type contact (NC orNO) required the device controllingyour generator Gen-set alarm LED goes but generator operating normally ATS010 detects short circuit between the terminals connectedto the alarm signal contact - Wiring error. - Wiringerror ABB SACE SACE ATS010 RH0202002 L2467. Make certain that you are usingthe correct type contact (NC orNO) required the device controllingyour - Generatorproblem. EmergencyLine LEDdoes not on even ifthe generator running ATS010 does not detect power emergency line. NETSENSOR PROBLEM DESCRIPTION POSSIBLE CAUSES Normal line voltage OKbutthe ATS010 indicates voltage too high or too low - DIP-switchratedvoltage regulation not correct - Minimum andmaximum voltages set with the trimmers areunsuitable for the rated voltage ofyour system - Wiringerrcr Only the orR TEDgoes on. "Not Auto” LED goes but the generator automatic mode ATS010 detects open circuit between the terminals connectedto the manual mode signal contact - relative terminal not connected "Not Auto" LED does not even if the generator set manual mode ATS010 detects short circuit between the terminals connectedto the manual mode signal contact - Wiring error. Two the phases havebeen inverted. The ATS010 workingin single-phasemode DIP-switchregulationof single/threephase operating mode not correct The device signals phase sequence inversion The ATS010 detects phase sequence contrary to what expected - Wiringerror. The generator always running Wiring error. Gen-set alarm LED does not ON even there alarm ATS010 detects open circuit between the terminals connectedto the alarm signal contact - Wiring error