ABB Jednotka řízení záskoku Návod k instalaci a provozu (4)

| Kategorie: Návody k obsluze Montážní návody  | Tento dokument chci!

Vydal: ABB s.r.o, ELSYNN Autor: ABB ELSYnn

Strana 112 z 185

Vámi hledaný text obsahuje tato stránku dokumentu který není autorem určen k veřejnému šíření.







Poznámky redaktora
Troubleshooting POWER ONAND SET-UP PROBLEM DESCRIPTION POSSIBLE CAUSES TheATS010does notturnon. "Withdrawn" LED does not on even the withdrawn ATS010 has detected short circuit the terminals connected the "CB withdrawn" signal auxiliary contact - Wiring error Trip LED goes ON, but the does not have protection trip relay ATS010 has detected open circuit the terminals connected the "relay tripped" signal auxiliary contact - the trip terminal for that has not been connected Trip LED goes ON, but the relay has not tripped ATS010 has detected open circuit the terminals connected the "relay tripped" signal auxiliary contact - Wiring error - The ATS010 has not been reset or rebooted (powered off and again) after last relay trip. Trip LED does not when CB relay tripped ATS010 has detected short circuit the terminals connected the "relay tripped" signal auxiliary contact - Wiring error ON LED remains off when the is opened and closed ATS010 has detected open circuit the terminals connected the "open/closed" signal auxiliary contact and thus considers the open - the closed terminal for that has not been connected ON LED remains red when the is opened and closed ATS010 has detected short circuit the terminals connected the "open/closed" signal auxiliary contact and thus considers the CB closed - Wiring error W hen using the front selector, the normal line does not open, or does not close The otor operators control coils not receive power - Wiring error - otor operators control coils are not powered ABB SACE SACE ATS010 RH0202002 L2467.5.3. auxiliarypowersupply electronic circuit - powersupply wiringerror - powersupply voltagetoolew - ATSis receiving24Vpower through48 Vterminals ATS continuallyrepeats starting secuence,turning onall LEDs Reset commandis constantly present Resetterminalis not wiredcorrectly CIRCUITBREAKERSTATE PROBLEM DESCRIPTION POSSIBLE CAUSES "Withdrawn" LED goes but the CB fixed version ATS010 has detected open circuit the terminals connected the "CB withdrawn" signal auxiliary contact - the withdrawn terminal for the in question has not been connected "Withdrawn" LED goes even when the the connected position ATS010 has detected open circuit the terminals connected the "CB withdrawn" signal auxiliary contact - Wiring error - The ATS010 has not been reset or rebooted (powered off and again) after the was last removed