Poznámky redaktora
- otherwise the unit starts the gen set switching sequence and supplies
powerfrom the generator.
The ATS010 unit starts operating automatic mode:
- ifnormal line voltage OK, the normal line circuit breaker remains
closed and powered.
TheATS State LED turnsyellow when logic not active and offwhen
logic active.
□ present plant, open and close the logic state input.
□ itch fro selector back ode.
The Normal line circuit breaker closes, and the LED turns red.
In this case press the “Logic ON-OFF”push button enable the logic.
□ itch fro selector utom atic position.
The Output contactfor Logic State closed when automatic logic is
active and open when logic disabled.
The green Emergency Line LED goes offindicating that the line not
powered.
The gen set stops (depending the characteristics ofyour plant, the
amount ftime requiredfor this may vary).
The LED the button turns green.
ATS State LED turnsyellow when logic not active and offwhen logic
is active.
□ itch fro selector orm al-Em ergency position.
The normal line circuit breaker closes.
Output contactfor Logic State closed when automatic logic active
and open when logic disabled.itch fro selector orm -Em ergency ff.
I fautomatic logic disabled, the LED the Logic ON/OFFpush button
is red.
When the remote switching command deactivated, normal line
ABB SACE SACE ATS010 RH0202002 L2467.
□ Press the push tto reboot the logic.
□ itch fro selector mode.
□ present plant, send the remote itch ing command.
The emergency line circuit breaker LED goes off.
Normal line circuit breaker ONLED turns red, indicating that the circuit
breaker closed.
The unit performs the switching procedure: starts the gen set,
commands the circuit breakers and begins supplying power through
the emergency line.
The green Emergency Line LED goes offindicating that the ATS010 is
sending the gen set stop command.
The normal line circuit breaker opens