Poznámky redaktora
□ itch fro selector back ode.
The emergency line circuit breaker LED goes off.itch fro selector orm -Em ergency ff.
□ itch fro selector mode.
Output contactfor Logic State closed when automatic logic active
and open when logic disabled.
The LED the button turns green.
The Output contactfor Logic State closed when automatic logic is
active and open when logic disabled.
ATS State LED turnsyellow when logic not active and offwhen logic
is active.
The normal line circuit breaker closes.
Normal line circuit breaker ONLED turns red, indicating that the circuit
breaker closed.
□ itch fro selector orm al-Em ergency position.
□ Press the push tto reboot the logic.
TheATS State LED turnsyellow when logic not active and offwhen
logic active.
The green Emergency Line LED goes offindicating that the line not
powered.
The ATS010 unit starts operating automatic mode:
- ifnormal line voltage OK, the normal line circuit breaker remains
closed and powered.
The normal line circuit breaker opens.
□ present plant, send the remote itch ing command.
When the remote switching command deactivated, normal line
ABB SACE SACE ATS010 RH0202002 L2467.
In this case press the “Logic ON-OFF”push button enable the logic.
□ present plant, open and close the logic state input.
The green Emergency Line LED goes offindicating that the ATS010 is
sending the gen set stop command.
- otherwise the unit starts the gen set switching sequence and supplies
powerfrom the generator.
I fautomatic logic disabled, the LED the Logic ON/OFFpush button
is red.
□ itch fro selector utom atic position.
The Normal line circuit breaker closes, and the LED turns red.
The unit performs the switching procedure: starts the gen set,
commands the circuit breakers and begins supplying power through
the emergency line.
The gen set stops (depending the characteristics ofyour plant, the
amount ftime requiredfor this may vary)