Test mode, the tables change llow assumed that gen set alarms are present and that the gen set autom atic mode. Test mode, strategy 1 From To CoCo ALGE Other conditions 1 0 1 power normal line for least 1 2 1 2 power normal line for least 1 3 Power Normal line for least T4 3 0 4 Power Normal line for least T4 4 1 4 Power supplied Gen-set for least T5 No power normal line 5 1 5 Power Normal line for least T4 State present for least T4 5 State present for least T4 5 power supply from Gen-set 6 X Test mode, strategy 2 F o CoCo ALGE Other conditions 1 0 2 1 2 power normal line for least T1 Power supplied Gen-set for least T5 3 Power Normal line for least T4 3 0 4 Power Normal line for least T4 4 1 4 Power supplied Gen-set for least T5 No power normal line 5 Power Normal line for least T4 5 Power Normal line for least T4 State present for least T4 5 Power Normal line for least T4 State present for least T4 5 Power supplied Gen-set for least T5 State present for least T4 5 Normal line not powered powered for less than T4 6 Power Normal line for least T4 ABB SACE SACE ATS010 RH0202002 L2467