utom atic mode, strategy 1
From To
CCD CoCo NoAu ALGE ther conditions
1 pow normal line for least T2
1 0
1 pow normal line for least T1
2 State present for least T3
Power Normal line for least T4
2 X
2 1
2 pow normal line for least T1
2 Power supplied Gen-set for least T5
3 Power Normal line for least T4
3 Power Normal line for least T4
3 Power Normal line for least T4
3 pow normal line for least T2
3 0
4 Power Normal line for least T4
4 X
4 1
4 Power supplied Gen-set for least T5
No pow normal line
4 Power supplied Gen-set for least T5
5 X
5 1
5 Power Normal line for least T4
State present for least T4
5 State present for least T4
5 pow supply from Gen-set
6 X
A utom atic mode, strategy 2
From To
CCD CoCo NoAu ALGE ther conditions
1 pow normal line for least T2
1 0
2 State present for least T3
Power Normal line for least T4
2 X
2 1
2 pow normal line for least T1
Power supplied Gen-set for least T5
2 Power supplied Gen-set for least T5
3 Power Normal line for least T4
3 Power Normal line for least T4
3 Power Normal line for least T4
3 pow normal line for least T2
3 0
4 Power Normal line for least T4
4 X
4 1
4 Power supplied Gen-set for least T5
No pow normal line
4 0
5 Power Normal line for least T4
5 Power Normal line for least T4
5 Power Normal line for least T4
State present for least T4
5 Power Normal line for least T4
State present for least T4
5 Power supplied Gen-set for least T5
State present for least T4
5 Normal line pow ered powered for less than T4
5 Normal line pow ered powered for less than T4
6 Power Normal line for least T4
ABB SACE SACE ATS010 RH0202002 L2467