Poznámky redaktora
Calibrations table “K” relais ■H Type UXAB code Release rated current C ircuit-breakers type O verload protection Delayed rt-circu protection In P2C PC3 current setting ranges I1=(0.5*1) A I2 current settings available ranges A B K 219499071 630 1250 1600 1 2 3 1250 1250 1600 - 315^630 625^1250 800^1600 1250^2500 2500^5000 3200^6400 1 1 1 2500^7500 5000^15000 6400^16000 2 2 2 K 219499080 2000 2000 2000 1000^2000 4000^8000 8000^20000 2 2500 2500 2500 1250^2500 5000^10000 7500^15000 2 K 219499089 3200 3200 3200 1600^3200 6400^12800 9600^19200 2 4000 4000 4000 2000^4000 8000^16000 12000^24000 2 4500 4500 4500 2250^4500 9000^18000 13500^27000 2 5000 5000 5000 2500^5000 10000^20000 18000^30000 2 Example The right code for the order release rated current 1250 Delayed short-circuit protection 5000-15000 is: UXAB 219499071 2 UXAB Code Rated current (colum Delayed rt-circu protection (colum B) UXAB219499071 2 ABB SACE ___________ /9 1SDC001007D0201 2 Otomax