Terminal blocks Klippon Connect 2025

| Kategorie: Katalog  | Tento dokument chci!

Vydal: Weidmüller, s.r.o.

Strana 501 z 872







Poznámky redaktora
Please note that brushes, files sandpaper may used, aluminium particles could stuck and thus transferred other conductors. 1 Scrape the conductor evenly on all sides. Note: The current carrying capacity and respective torques for the connection of aluminum wires the terminal blocks must always observed. 2 Cover the conductor all around with neutral grease. B. Immediately after removing the oxide layer, the end the conductor has be rubbed with neutral grease (for example with acid and alkali free vaseline) and connected the terminal immediately. 3 Direct connection our WPD blocks with specified torque.39 CAT1 Version 2025 Application range B .g.Power feed-in Screw connection Professional processing and handling aluminium conductors for direct connection In order ensure optimal connection solid and sectional core aluminium conductors, the stripped end the conductor must cleaned the oxide layer immediately scraping, e. These can be found the respective data sheet the online catalog. the conductor has been disconnected and reconnected, the work steps have repeated. with knife