(11)Write any value abort any remote programming write operation and back
to previous values.SCHRACK TECHNIK GMBH 18
If necessary back the old parameters saved EEPROM, mandatory send also
these following messages :
1) write word 0x5AA5 address 0x2700
2) write word 0xYYYY address 0x2800 any value )
If necessary save new parameters EEPROM mandatory send these following
messages :
1) write word 0x5AA5 address 0x2700
2) write word 0xYYYY address 0x2600 any value )
WRITE ADDRESS TABLE
(7)This value V/10 For instance, write have KTV 5.0
(8)To reset desired measurements write the following word (in binary:
0|0|0|0|0|0|0|0|0|0|b6|b5|b4|b3|b2|b1|b0
b0 Reset Hour Meter
b1 Reset Maximum Powers
b2 Reset Maximum Voltages
b3 Reset Maximum Currents
b4 Reset Minimum Voltages
b5 Reset Active Partial Energy
b6 Reset Reactive Partial Energy
b7 b15 0
(9)Write any value save the new parameters changed Remote commands
(10)To any remote programming write operation, it’s mandatory write safety
key 0x5AA5