Medium voltage DC (MVDC) grids for an all-electric society

| Kategorie: Firemní tiskovina  |

Vydal: Neurčeno Autor: Tým odborníků IEC

Strana 31 z 90

Jak získat tento dokument?






Poznámky redaktora
Unlike MVAC systems, system inductance MVDC networks does not limit the peak current; only affects the short- circuit current’s time constant.1 Differences between and DC fault management MVDC power primarily supplied via AC/DC or DC/DC converters, which typically include built- in overcurrent protection prevent currents exceeding 150% the converter’s rated value. 4. Thus, fault detection and isolation MVDC systems must be completed within protect the converter. 4. MVAC systems, primary components such transformers and synchronous generators can withstand fault currents that are tens times their rated current from tens hundreds milliseconds (ms).1 Fault current management Managing fault currents, like short circuits and overloads, critical task any power grid. The most important considerations are detailed the following sections.1. These differences occur across the entire power system from major components and system design the methods used manage power system operation. Alternatively, MVDC converter stations might fail withstand the fault current, leading to extensive damage and prolonged power outages. This limitation reduces the fault current available from MVDC-based generator, making fault detection more challenging grid sections far from the generator.1. By contrast, semiconductor switches used DC power converters typically tolerate only twice their rated current for less than ms.31 Section 4 MVDC technologies and operational considerations The unique characteristics MVDC result major differences the core technologies and operational methods used MVDC power systems compared to their counterparts. Timing much more critical MVDC systems than MVAC systems. higher voltages, most existing AC fault current management devices fail to interrupt currents the required fault levels. Converter stations might shut down protect themselves during fault event, potentially causing power outages across the entire power system, not just the faulted segment. result, short circuit currents MVDC systems rise more quickly than systems. Consequently, fault isolation becomes more difficult. Because power systems provide continuous current with natural zero-crossings, fault currents continue rise their peak without zero- crossings, making current interruption switching far more difficult. In MVDC systems, the polarity the supply voltage remains constant, short-circuit current will increase exponentially and monotonically, limited only the supply voltage and the resistance of the short-circuit fault. Fault current management systems differs substantially from that systems, explored in the following sections 4. Fault current management generally involves fault detection, fault isolation, and post-fault reconfiguration. . Detection and isolation are needed to separate the faulted branch from the unaffected sections the power system, while reconfiguration is required minimize the interruption power flow neighbouring loads