4
Applicable standards:
Flame-retardant acc.:
44 Ohm/km max.:
5 GOhm km
Insulation resistance, min. 8,0 0,3 mm
Cable external diameter:
Orange
Outer sheath colour:
Electrical data
100 Ohm Ohm
Characteristic impedance:
22 Ohm/km
Conductor resistance, max.1/2,55-100 LI
Cable structure
Copper, bare (AWG 18/7)
Inner conductor diameter:
PO
Core insulation:
or, bl
Core colours:
2 cores fillers stranded together
Stranding element:
Polyester foil over stranded bundle
Shielding 1:
Polyester foil, aluminium-lined
Shielding 2:
Cu braid, tinned
Total shielding:
yes
Drain wire:
PVC
Outer sheath material:
app. kg/km
Weight:
80 mm
bending radius, repeated:
-40°C
Operating temperature range min.:
1,22 MJ/m
Caloric load, approx. IEC 60332-3
CMG 75°C PLTC FT4
UL Style:
CSA 4
CSA standard:
Application
HELUKABEL® FOUNDATION™ Fieldbus Basic for normal requirements this industrial networks.
720
Data, Network and Bus Technology HELUKABEL BUS-Cables
®
. Thanks use stranded conductors, this cable can
be moved occasionally and satisfies the usual American requirements for such networks. value:
45,00 kg/km
Copper weight:
Norms
Foundation Fieldbus Spec.
Dimensions and specifications may changed without prior notice. FF-816-1.
Mutual capacitance:
300 V
Nominal voltage:
1,5 kV
Test voltage:
Attenuation: dB/km
3,4
ื
kHz
39
Technical data
app.
803354, Foundation™ Fieldbus Basic
Part no.BUS Cables
FOUNDATION™ Fieldbus
Basic
process automation
Type
1x2x1.:
+80°C
Operating temperature range max.
Loop resistance:
60 nF/km nom