mm²
Part no. +90°C Outer extrusion semi-conducting coating
spliced with the XLPE-insulation
Ⴠ Short circuit temperature
core +250°C
screen +350°C (duration)
(short circuit duration max. s)
Ⴠ Conductive wrapping
Ⴠ Installation notes
To guarantee optimum operating
reliability the extruded semi-conductive
layer spliced with the insulation for long
duration. 6/10kVXLPE-insulated, Cu-conductor, PVC-sheath
Properties
Cable structure
Technical data
Ⴠ Bare copper-conductor, to
DIN VDE 0295 cl. (RQ03)
602
Energy- and Power Cable Medium Voltage Power Cables
.
Ⴠ Conversion factors for laying air
Ⴠ Air temperature/Conversion factor
15°C/1,12; 20°C/1,08; 25°C/1,04;
30°C/1,0; 35°C/0,96; 35°C/0,96; 40°C/
0,91; 45°C/0,87; 50°C/0,82;
Application
Suitable for installation indoors and cable ducts, outdoors with protected laying, well for laying racks for industrial and switching systems
and power plants. DIN VDE 0276 and IEC 60502
Ⴠ round conductor, multi-wire
Ⴠ AWG sizes are approximate equivalent
values.
AWG-No.c. The actual cross-section mm².
Ⴠ Conversion factors for laying earth
especially for laying bundle form and
other requirements are noted in
DIN VDE 0298 part and 0276 part 1000.cores x
cross-sec.
mm²
Insulation
thickness
mm
No. Limited use when buried the earth the PVC outer sheath could damaged high mechanical stress. Extruded sheath over three cores
Ⴠ Test voltages Outer sheath PVC
compound type DMV6 620 S2
Ⴠ Test voltages d.
Ⴠ For laying earth: For ground thermal
resistivity Kxm/W, laying depth 0,7 m,
ground temperature 20°C, EVU load
grade 0,7.
Ⴠ Screen: Braiding copper wires with one
or two tapes applied helically
Ⴠ Nominal voltages U0/U 6/10 cores stranded
Ⴠ Operating voltages max.N2XSEY . kV
Ⴠ Sheath colour red
Ⴠ Minimum bending radius
15x cable Note
Ⴠ Tests
acc. km
Cop.
The inner conducting layer between the conductor and the XLPE insulation and the firmly bonded outer conducting layer the XLPE insulation assures
a construction free partial discharges with high operational reliability. For this reason recommend
a peeling tool for installation.
4
2850,0
1046,0
43,0
2,5
16
3,4
rm 16
3 25
34339
2
3300,0
1210,0
48,0
2,5
16
3,4
rm 16
3 35
34340
1
3750,0
1671,0
50,0
2,5
16
3,4
rm 16
3 50
34341
2/0
4650,0
2250,0
54,0
2,6
16
3,4
rm 16
3 70
34342
3/0
5700,0
2995,0
58,0
2,8
16
3,4
rm 16
3 95
34343
4/0
6700,0
3715,0
61,0
2,9
16
3,4
rm 16
3 120
34344
300 kcmil
7900,0
4638,0
65,0
3,0
25
3,4
rm 25
3 150
34345
350 kcmil
9200,0
5645,0
68,0
3,1
25
3,4
rm 25
3 185
34346
500 kcmil
11450,0
7274,0
74,0
3,3
25
3,4
rm 25
3 240
34347
600 kcmil
14450,0
9160,0
79,0
3,3
25
3,4
rm 25
3 300
34348
Dimensions and specifications may changed without prior notice.
weight
kg km
Outer Ø
app.2, multi-wire,
BS 6360 cl...2, IEC 60228 cl.2
Ⴠ Ⴠ
Three core XLPE-insulated
power cables DIN VDE 0276
and IEC 60502
The materials used manufacture are
cadmium-free and contain silicone
and free from substances harmful to
the wetting properties lacquers
Ⴠ Ⴠ
Temperature range
during installation -5°C
Inner semi-conducting coating
Tests
Ⴠ Core insulation cross-linked polyethylene
(XLPE) self-extinguishing and flame retardant
acc. DIN VDE 0482-332-1-2,
DIN 60332-1-2, IEC 60332-1 (equivalent
DIN VDE 0472 part 804 test method B)
Ⴠ Operating temperature
max. mm
Sheath
thickness
Nominal value
mm
Screen
cross-sec.
Ⴠ For laying air: Air temperature 30°C, EVU
load grade 1,0.
Weight
app