1 cl. Tests acc.to DIN VDE 0472
part 814 IEC 60331.
The functionality for minutes assures
when persons and animals are saved
from burning building.1 cl. AWG-No.
Ⴠ LS0H Low Smoke Zero Halogen
Application
Security cables are ideal for use everywhere, where case fire human life and material assets are protected and safety conciousness take a
special significance, industrial complexes, power stations, communal establishment, hotels, airports, underground railway networks, hospitals
and outpatients clinic (DIN VDE 0107), department stores, data processing centres, theaters, cinemas, multi-storey buildings, public gatherings,
schools etc.
Insulation integrity under direct
flame propagation for the test period
of 180 minutes. This fulfils the demands
of technical guide lines for fire protection
(supplement DIN VDE 0108 part 1).
The cables are suitable for fixed installation dry and moist rooms, in, above, and beneath plaster well masonary walls and concrete. km
Cop.N2XH-FE 180/E 30security cable, halogen-free, 0,6/1 kV, with improved fire
characteristics
Properties
Cable structure
Technical data
Ⴠ Bare copper-conductor, to
DIN VDE 0295 cl.
For the installation conduit all precautions must taken that accumulation water can occur the pipes.
mm²
Part no.
= The product conformed with the Low-Voltage Directive 2006/95/EC.
12
155,0
38,0
8,0
1 re
52058 2
460,0
336,0
14,0
1 rm
52063
1
590,0
480,0
15,5
1 rm
52064
10
190,0
58,0
9,0
1 re
52059
8
215,0
96,0
10,0
1 re
52060 2/0
820,0
672,0
17,5
1 rm
52065
3/0
1090,0
912,0
19,5
1 rm
52066
6
240,0
154,0
10,5
1 re
52061
4
380,0
240,0
13,0
1 rm
52062 4/0
1350,0
1152,0
21,0
1 120 rm
52067
Continuation Ⴇ
563
Energy- and Power Cable Low Voltage and Security Cables
Q
.1 cl.
weight
kg km
Outer Ø
app.2,
IEC 60228 cl. minutes
secures the functional performance the
fire warning and alarm systems, safety and
spare lighting, passenger lifts with
evacuation circuits, except the cables which
are installed within the ladder shafts and
engine rooms. (DIN VDE 0108), mining works, offshore plants, leading centres, traffic communication, emergency power supply and alarm systems. DIN VDE 0482
part 267, DIN 50267-2-1, IEC 60754-1
(equivalent DIN VDE 0472 part 815)
Ⴠ Smoke density acc. DIN VDE 0482 part 267,
DIN 50267-2-2, IEC 60754-2
(equivalent DIN VDE 0472 part 813)
Ⴠ Halogen-free acc. mm
No. to
DIN VDE 0482-332-3, 4066 part 3,
DIN 60332-3, IEC 60332-3 (previously
DIN VDE 0472 part 804 test method C)
Ⴠ 30: Functionality electrical cable
systems for minimum minutes. DIN VDE 0482
part 1034-1+2, DIN 61034-1+2,
IEC 61034-1+2, 7622 part 1+2
(previously DIN VDE 0472 part 816)
Note
Ⴠ round conductor, single-wire
rm round conductor, multi-wire
Ⴠ AWG sizes are approximate equivalent
values.
Weight
app. Test to
DIN 4102 part 12.2, single-wire
or multi-wire, 6360 cl.cores x
cross-sec. mm
No. The actual cross-section mm². km
Cop.cores x
cross-sec.
Caloric load values
see Technical Informations
Ⴠ Sheath colour orange
Tests
Ⴠ Flame test acc.
weight
kg km
Outer Ø
app.2
Ⴠ Ⴠ
Halogen-free security cable with improved
characteristics the case fire to
DIN VDE 0266
Halogen free, separation corrosive
and toxic gases
Ⴠ Flame retardant and hardly flammable
Ⴠ Temperature range
-30°C +70°C
Ⴠ Self-extinguished and fire resistant
Ⴠ Core insulation cross-linked
polyethylene, compound type 2XI1 to
DIN VDE 0276 part 604
Ⴠ flame propagation, therefore security
from fire
Ⴠ Permissible operating temperature
at conductor +90°C low smoke density, low impairment of
escape routes and fire extinguishing
activities
Ⴠ Core identification DIN VDE 0293-308
and 0276 part 604
Ⴠ Nominal voltage U0/U 0,6/1 kV
Ⴠ Test voltage 4000 V
Ⴠ GN-YE conductor, cores and above Toxicological harmless
Ⴠ Minimum bending radius
15x cable Cores stranded layers self-ignition
Ⴠ Overall core covering, halogen-free filling
compound, pressed
Ⴠ Radiation resistance
up 200x106 cJ/kg (up 200 Mrad)
Ⴠ Maintenance functionality during the
increased current load
Ⴠ Outer sheath thermoplastic halogen-free
polyolefine, flame retardant
Ⴠ
Ⴠ 180: Insulation integrity for 180
minutes.
mm²
Part no.
Weight
app.
Ⴠ Corrosiveness combustion gases
acc.
AWG-No